Limitation on/off (p0784)
With the "Limitation" drop-down list, select whether the output value of the measuring socket
is to be restricted to the limit values of the characteristic curve for the required measuring
socket.
1. Select one of the following settings in the "Limitation" drop-down list of a measuring
socket:
– Limitation On
– Limitation Off
Select signal source for T0, T1 and T2
The signal to be output via a measuring socket is specified by interconnecting a signal
source p0771[0...2].
Table 4- 3
r0060
r0063
r0069[0...2]
r0075
r0076
r0077
r0078
1. Select the signal sources whose signal is to be output via the measuring socket for the
respective measuring sockets T0, T1 and T2.
Commissioning with Startdrive
Commissioning Manual, 11/2017, 6SL3097-4AA10-0BP1
If signals are output outside the permissible measuring range, the signal is limited to
4.98 V or to 0 V.
The output of signals outside the permissible measuring range causes a signal
overflow. In the event of an overflow, the signal jumps from 0 V to 4.98 V or from 4.98
to 0 V.
Important measuring signals (examples):
CO: Speed setpoint before speed setpoint filter
CO: Actual speed value
CO: Actual phase currents value
CO: Field-generating current setpoint
CO: Actual field-generating current value
CO: Torque-generating current setpoint
CO: Actual torque-generating current value
4.7 Basic parameterization of the drive objects