B4: Timer Function; B5: Pid Control - YASKAWA P1000 Quick Start Manual

Hide thumbs Also See for P1000:
Table of Contents

Advertisement

b4: Timer Function

u
No.
(Addr.
Name
Hex)
b4-01
Timer Function On-Delay
(1A3)
Time
b4-02
Timer Function Off-Delay
(1A4)
Time

b5: PID Control

u
No.
(Addr.
Name
Hex)
b5-01
PID Function Setting
(1A5)
b5-02
Proportional Gain Setting
(1A6)
(P)
b5-03
(1A7)
Integral Time Setting (I)
b5-04
(1A8)
Integral Limit Setting
b5-05
(1A9)
Derivative Time (D)
b5-06
(1AA)
PID Output Limit
b5-07
(1AB)
PID Offset Adjustment
b5-08
PID Primary Delay Time
(1AC)
Constant
b5-09
PID Output Level Selection
(1AD)
b5-10
(1AE)
PID Output Gain Setting
b5-11
PID Output Reverse
(1AF)
Selection
b5-12
PID Feedback Loss
(1B0)
Detection Selection
b5-13
PID Feedback Loss
(1B1)
Detection Level
YASKAWA ELECTRIC TOEP YAIP1U 01B YASKAWA AC Drive - P1000 Quick Start Guide
Sets the on-delay and off-delay times for a digital timer output
(H2-oo=12).
The output is triggered by a digital input programmed to
H1-oo=18).
0: Disabled
1: Enabled (PID output becomes output frequency reference, deviation D
controlled)
Sets the proportional gain of the PID controller.
Sets the integral time for the PID controller.
Sets the maximum output possible from the integrator as a percentage of the
maximum output frequency.
Sets D control derivative time.
Sets the maximum output possible from the entire PID controller as a
percentage of the maximum output frequency.
Applies an offset to the PID controller output. Set as a percentage of the
maximum output frequency.
Sets a low pass filter time constant on the output of the PID controller.
0: Normal output (direct acting)
1: Reverse output (reverse acting)
Sets the gain applied to the PID output.
0: Negative PID output triggers zero limit.
1: Rotation direction reverses with negative PID output.
Note:
When using setting 1, make sure reverse operation is permitted
by b1-04.
0: No fault. Digital output only.
1: Fault detection. Alarm output, drive continues operation.
2: Fault detection. Fault output, drive output is shut off.
3: No fault. Digital output only. No fault detection when PID control is
disabled.
4: Fault detection. Alarm is triggered and drive continues to run. Fault
detection even when PID is disabled.
5: Fault detection. Drive output shuts off. No fault detection when PID control
is disabled.
Sets the PID feedback loss detection level as a percentage of the maximum
output frequency.
Description
Description
B.2 b: Application
Values
Page
Default: 0.0 s
Min.: 0.0
Max.: 3000.0
Default: 0.0 s
Min.: 0.0
Max.: 3000.0
Values
Page
Default: 0
Range: 0, 1
Default: 1.00
Min.: 0.00
Max.: 25.00
Default: 1.0 s
Min.: 0.0
Max.: 360.0
Default: 100.0%
Min.: 0.0
Max.: 100.0
Default: 0.00 s
Min.: 0.00
Max.: 10.00
Default: 100.0%
Min.: 0.0
Max.: 100.0
Default: 0.0%
Min.: -100.0
Max.: 100.0
Default: 0.00 s
Min.: 0.00
Max.: 10.00
Default: 0
Range: 0, 1
Default: 1.00
Min.: 0.00
Max.: 25.00
Default: 0
Range: 0, 1
Default: 0
Range: 0 to 5
Default: 0%
Min.: 0
Max.: 100
187
B