Samson TROVIS 5573 Mounting And Operating Instructions page 69

Automation system trovis 5500 heating and district heating controller
Table of Contents

Advertisement

Functions
Storage tank sensor SF1
Thermal disinfection
WE
Configuration
1
CO4 -> F01 - 1
0
CO4 -> F14 - 1
3
Day of the week / 1–7, 1, 2, ..., 7 with
1–7 = daily, 1 = Monday, ..., 7 = Sunday
00:00
Start time / 00:00 to 23:45h; in steps of 15 minutes
04:00
Stop time / 00:00 to 23:45h; in steps of 15 minutes
70.0 °C
Disinfection temperature / 60.0 to 90.0 °C
10.0 °C
Set point boost / 0 to 50 °C
0 min
Hold time of disinfection time / 0 to 255 min
bE=1
bE=1, bE=0 (start of disinfection with terminal 03/12 =
ON, OFF; only applies when Start time = Stop time)
Functions of the DHW circuit