Functions Of The Heating Circuit; Functioning Principle; Weather-Compensated Control - Samson TROVIS 5179 Mounting And Operating Instructions

District heating controller
Table of Contents

Advertisement

5

Functions of the heating circuit

Which controller functions are available depends on the selected system code number (Anl).

5.1 Functioning principle

The heating circuit with the highest flow set point has priority. This principle applies to all heat-
ing circuits with mixing valves. In systems Anl 3, 5 and 8, the pump circuit has priority. The flow
set point of the heating circuit with priority is controlled by the valve in the pre-control circuit.
If several heating circuits have the same flow set point, the heating circuit with lowest number al-
ways has priority and is controlled by the primary valve.

5.2 Weather-compensated control

When weather-compensated control is used, the flow temperature is controlled according to the
outdoor temperature. The heating characteristic in the controller defines the flow temperature
set point as a function of the outdoor temperature (–> Fig. 2).
[
˚
C]
t
VL
130
120
110
100
90
80
70
60
50
40
30
20
20
16
Fig. 2 · Gradient characteristics
Function
Outdoor sensor AF1, 2, 3
12
8
4
0
-4
WE
3.2
2.9
2.6
2.4
2.2
2.0
1.8
1.6
1.4
1.2
1.0
0.8
0.4
0.2
t
A
-8
-12
-16
-20
[
˚
C]
Configuration
Co1, 2, 3 -> Fb02 = ON*
* Co1 -> Fb02 cannot be deactivated
Functions of the heating circuit
t
Flow temperature
VL
t
Outdoor temperature
A
EB 5179 EN