Functions Of The Heating Circuit; Weather-Compensated Control - Samson TROVIS 5575 Mounting And Operating Instructions

Automation system trovis 5500 heating and district heating controller
Table of Contents

Advertisement

Functions of the heating circuit

5
Functions of the heating circuit
Which controller functions are available depends on the selected system code number (Anl).
5.1

Weather-compensated control

When weather-compensated control is used, the flow temperature is adjusted depending on
the outdoor temperature. The heating characteristic in the controller defines the flow temper-
ature set point as a function of the outdoor temperature (–> Fig. 5). The outdoor temperature
required for weather-compensated control can either be measured at an outdoor sensor or
transmitted from a connected device bus.
˚
t
[
C]
VL
130
120
110
100
90
80
70
60
50
40
30
20
20
16
Fig. 5 · Gradient characteristics
Functions
Outdoor sensor AF1
Receive value from AF2
50
EB 5575 EN
12
8
4
0
-4
WE
1
0
3.2
2.9
2.6
2.4
2.2
2.0
1.8
1.6
1.4
1.2
1.0
0.8
0.6
0.4
0.2
t
A
˚
-8
-12
-16
-20
[
C]
Configuration
CO1 -> F02 - 1
CO7 -> F09 - 1; register no.
t
Flow temperature
VL
t A
Outdoor temperature