Indicators - Omron SYSMAC CS Series Operation Manual

Profibus master units
Hide thumbs Also See for SYSMAC CS Series:
Table of Contents

Advertisement

Unit Components
2-1-2

Indicators

Indicator Specifications
Indicator
RUN
ERC
(PROFIBUS Master Unit
Error)
ERH
(PLC Error)
PRM
(Parameter database)
BST
(Bus status)
COMM
(I/O Data communication)
BF
(Bus Fail)
The CS1/CJ1W-PRM21 PROFIBUS Master Units are each fitted with seven
LEDs to indicate the operational mode and status of the Unit and the PROFI-
BUS network
CS1W-PRM21
PRM21
RUN
RUN
ERC
ERC
ERH
ERH
BST
BST
PRM
PRM
BF
BF
COMM
COMM
Colour
Status
Green
Not lit
• Startup test failed, Unit not operational.
• Operation stopped, due to a fatal error.
Lit
Initialization successful, Unit is in normal operation.
Red
Not lit
Unit is in normal operation.
Lit
One of the following errors occurred:
• Startup error.
• Non-volatile memory error (checksum failed, write-verify failed).
• Invalid PROFIBUS parameter configuration setting.
• Fatal error in program execution.
Red
Not lit
PLC CPU in normal operation.
Lit
One of the following errors occurred:
• PLC CPU Bus error.
• Cyclic Refresh Monitor Time-out.
• Routing table error.
Green
Not lit
PROFIBUS Parameter configuration is not available or incorrect.
Flashing PROFIBUS Parameter configuration is being transferred to the Unit
and is not yet available.
Lit
PROFIBUS Parameter configuration is correct, and operational.
Green
Not lit
The PROFIBUS Master Unit is in OFFLINE or STOP mode.
Flashing The PROFIBUS Master Unit is in CLEAR mode.
Lit
The PROFIBUS Master Unit is in OPERATE mode.
Green
Not lit
No PROFIBUS data exchange with any of the allocated slaves.
Flashing Fatal error occurred (ERC LED is ON). Unit initialization failed.
Lit
PROFIBUS data exchange ongoing with at least one allocated slave.
Red
Not lit
No PROFIBUS communication errors occurred.
Flashing At least one allocated slave is not in data exchange with the Unit.
An error occurred in the PROFIBUS interface of the Unit (see section 7-
Lit
2 Troubleshooting Using LED Indicators).
Note Unless otherwise specified, the frequency of a flashing LED is 1 Hz (50% duty
cycle).
CJ1W-PRM21
PRM21
RUN
ERC
CS
CS
ERH
Meaning
Section 2-1
PRM
COMM
BST
BF
29

Advertisement

Table of Contents
loading

This manual is also suitable for:

Sysmac cj-seriesSysmac cj1w-prm21Sysmac cs1w-prm21