Setting up a network
Using Drag & Drop
1,2,3...
Using the Add Device Button
1,2,3...
1. Open the Device Catalogue: Either select the View - Device Catalogue
menu option, or press the
2. Select a device DTM in the Device Catalogue.
3. Left click the mouse and Drag the mouse pointer to the desired location in
the network, i.e. MyNetwork in the Network view.
4. Release the mouse button and the device DTM will be added to that loca-
tion.
Note Master DTMs can only be added to the main branch of the Network.
Slave Device DTMs can only be added to Master DTMs. Whether or
not a DTM can be added to the branch is indicated by the cursor:
indicates no addition,
1. Select the top of the network to which the DTM must be added, i.e. select
MyNetwork in the Network view.
2. Open the device Catalogue: Either select the View - Device Catalogue
menu option, or press the
3. Select the device that must be added to the network.
4. Select the Add Device button at the bottom of the Device Catalogue win-
dow. The device DTM is added to the network.
Note If a DTM is selected in the Device Catalogue, which can not be add-
ed to the current location in the network, the Add Device button will
be disabled, which is shown as a grayed out button.
Note When adding a CS1/CJ1W-PRM21 Master DTM to the network, it is automat-
ically assigned the PROFIBUS network address 1. This address can be
changed, after opening the CS1/CJ1W-PRM21 Master DTM.
After adding the Master DTM to the Network view, repeat (one of) the proce-
dures as outlined above to add slave DTMs to the Master DTM. In the proce-
dures above, the highest level for adding slave DTMs is the Master DTM.
Note When adding slave DTMs to the CS1/CJ1W-PRM21 Master DTM, they are
automatically assigned their PROFIBUS network addresses, in ascending
order, i.e. the first slave is assigned address 2, the second address 3, etc. The
addresses can be changed in the slave DTM User Interface.