Omron SYSMAC CS Series Operation Manual page 119

Profibus master units
Hide thumbs Also See for SYSMAC CS Series:
Table of Contents

Advertisement

Generic Slave Device DTM
Module Configuration
Note
98
Note In case a changed address is invalid, for example if there is already another
slave device with the same new address, the Master DTM will set the number
back to its old value.
The Watchdog value is the value used by the slave device to monitor commu-
nication from the Master Unit. If no messages are sent to the slave by its Mas-
ter within the Watchdog timeout time, the slave device will stop data
exchange and switch back to the fail safe mode.
Note In the current version of CX-Profibus, the Watchdog setting made in the
Generic Slave DTM is overruled by the Watchdog setting in the Master DTM
(see also section 6-4-2 Setting the Bus Parameters).
The I/O module configuration defines the I/O Data which the slave will be
exchanging with the Master Unit, when it is in data exchange mode. The
upper window in the Configuration tab contains all possible modules, which
are in the GSD file. The lower window holds all selected I/O modules.
The user has to select the modules, which are associated with the physical
configuration of the slave device. Selecting, i.e. copying the module from the
upper window to the lower window can be done in several ways.
• Double-click the left mouse button on the selected module in the upper
window.
• Select the module in the upper window and click the Insert button or
Append button. Insert will insert the module above the row selected in the
lower window. Append will add the module to the end of the selected
module list.
1. The user can select multiple rows (in both windows) by simultaneously
holding the SHIFT or CTRL key on the keyboard and selecting the rows
using the left mouse button.
2. The amount of I/O modules and data which can be selected depends on
the slave device. The four rows of information above the module display
the maximum amounts as well as the selected totals.
Removing one or more selected modules from the list is done by
• double-clicking the left mouse button on the module in the lower window.
• selecting the module in the lower window and click the Remove button. In
this case selecting multiple modules is also possible.
Section 3-5

Advertisement

Table of Contents
loading

This manual is also suitable for:

Sysmac cj-seriesSysmac cj1w-prm21Sysmac cs1w-prm21