Error Codes - Omron SYSMAC CS Series Operation Manual

Profibus master units
Hide thumbs Also See for SYSMAC CS Series:
Table of Contents

Advertisement

Troubleshooting Using the Error Log
7-5-2

Error Codes

Error
Meaning
code
0001
Watchdog timer error in CPU
Unit.
0002
CPU Unit service monitor error.
000E
PLC Bus error.
0011
Event time out
0012
CPU Unit memory error
010D
Destination address not in rout-
ing tables (send failed)
010E
No routing table entry (send
failed)
010F
Routing table error (send failed)
0110
Too many relay points (send
failed)
0112
Header error (send failed)
0120
Unexpected routing error
0202
PROFIBUS parameter set
invalid.
020C
Protocol error.
0211
Duplicate master address.
0219
Hardware error.
The error codes are described in the following table. The detailed error code
will provide detailed information on an error.
Detailed error code
1st byte
00
00
Actual monitoring time ms (Hex)
00
00
MRC
SRC
01: Read error
03: Routing
table
02: Write error
Commands
Bit 15:
OFF
Bits 08 to 14:
SNA
Bits 00 to 07
SA1
Responses
Bit 15:
ON
Bits 08 to 14:
DNA
Bits 00 to 07
DA1
00
80: Bus param-
eter error
00 ~ 7D: Slave
parameter error
00
00 ~ 7D: Fail-
ing Master
Address
00
00 ~ 7D: Fail-
ing Master
Address
00
00
Correction
2nd byte
Replace the PLC CPU Unit.
Check the operating environment. Saved
Replace the CPU Unit.
Replace the CPU Unit.
01: Recreate the data specified by
the 2nd byte of the detailed error
code.
02: Clear memory using proce-
dure in the PLC operation manual.
Set the destination address in the
routing tables.
Set the local node, remote node
and relay nodes in the routing
tables.
Create the routing tables cor-
rectly.
Reconstruct the network or cor-
rect the routing tables so that
commands are set to within a 3-
level network range.
Check the command format and
set the correct command data.
Check the routing tables.
• Check the parameter settings.
• Re-download the configuration
if necessary.
Check the master devices on the
network, and make sure they are
all working correctly.
Check the master devices on the
network and ensure that they
have unique device addresses.
• Check the network wiring, and
make sure it is correct.
• Check for short-circuits.
• Check the bus timing set
through CX-Profibus.
• Check the HSA setting in CX-
Profibus, and make sure it is
set to the master device with
the highest address on the net-
work.
• Check if any other faulty
devices are on the same net-
work.
• Verify that the Highest Station
Address setting includes any
other master address on the
bus.
Section 7-5
Non-
volatile
Saved
Saved
Saved
Saved
---
---
---
---
---
---
---
---
---
---
223

Advertisement

Table of Contents
loading

This manual is also suitable for:

Sysmac cj-seriesSysmac cj1w-prm21Sysmac cs1w-prm21

Table of Contents