Master Status 2 (Word N+6) - Omron SYSMAC CS Series Operation Manual

Profibus master units
Hide thumbs Also See for SYSMAC CS Series:
Table of Contents

Advertisement

Allocated CIO Area Words
4-2-5

Master Status 2 (Word n+6)

Word n+6 [n = CIO 1,500 + (25 x unit number)]
Bit
Name
00
Disturbed Bus
ON
error
OFF
01
PROFIBUS proto-
ON
col error
OFF
02
Double Master
ON
address error
OFF
03
Hardware error
ON
OFF
04
Reserved by sys-
---
to
tem
11
120
The Master Status 2 word collects all error information on the Unit master
function. The status information is collected in the Master Status 1 word.
The contents of the Master Status 2 word (Word n+6) are:
15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
Word n+6
Status
Controlled
by
Unit
When turned ON, the Disturbed Bus error indicates that distorted mes-
sages have been received by the Unit. This may occur if the network is
not properly terminated or a cable is used, which is too long for the
selected baud rate.
Unit
Indicates that no Disturbed Bus error has occurred.
Unit
The PROFIBUS Protocol error flag will be turned ON if an error has
occurred in the protocol handling, e.g. a transmitted token frame could
not be read back.
Note In case this error occurs, the Unit will automatically switch to
Unit
Indicates that no PROFIBUS protocol error has occurred.
Unit
The Double Master Address error flag will be turned ON if there is
another master on the bus with the same with the same device address
as the CS1/CJ1W-PRM21.
Note In case this error occurs, the Unit will automatically switch to
Unit
Indicates that no Double Master Address error has occurred.
Unit
The Hardware error flag will be turned ON if an error has occurred on
the bus, e.g. message exceeding 256 bytes, broken messages, faulty
bus timing or devices beyond the HSA have been detected.
Note In case this error occurs, the Unit will automatically switch to
Unit
Indicates that no Hardware error has occurred.
---
These bits will be set to OFF by the Unit.
Unit operation
OFFLINE mode.
OFFLINE mode.
OFFLINE mode.
Section 4-2
Disturbed bus error
PROFIBUS protocol error
Double Master address error
Hardware error
Mode command error
Parameter error

Advertisement

Table of Contents
loading

This manual is also suitable for:

Sysmac cj-seriesSysmac cj1w-prm21Sysmac cs1w-prm21