Cio Area Word Allocations; Dm Area Word Allocations - Omron SYSMAC CS Series Operation Manual

Profibus master units
Hide thumbs Also See for SYSMAC CS Series:
Table of Contents

Advertisement

Overview of Word Allocations
4-1-1

CIO Area Word Allocations

4-1-2

DM Area Word Allocations

Software switches, PROFIBUS Master Unit status, and Slave Status data are
allocated in the CIO Area according to the unit number, as shown below. Soft-
ware switches are bits used as commands from the PLC CPU to the PROFI-
BUS Master Unit to enable executing Unit functions.
Unit number
Allocated words
0
CIO 1500 to CIO 1524
1
CIO 1525 to CIO 1549
2
CIO 1550 to CIO 1574
3
CIO 1575 to CIO 1599
4
CIO 1600 to CIO 1624
5
CIO 1625 to CIO 1649
6
CIO 1650 to CIO 1674
7
CIO 1675 to CIO 1699
The DM area words which are allocated for the PROFIBUS Master Unit are
not used, i.e. no data is exchanged between an allocated DM area and the
Unit. However, the allocated area is reserved for use in a future extension of
the Unit. Therefore, using this area for user data is not recommended.
Unit number
Allocated words
0
D30000 to D30099
1
D30100 to D30199
2
D30200 to D30299
3
D30300 to D30399
4
D30400 to D30499
5
D30500 to D30599
6
D30600 to D30699
7
D30700 to D30799
Unit number
Allocated words
8
CIO 1700 to CIO 1724
9
CIO 1725 to CIO 1749
10
CIO 1750 to CIO 1774
11
CIO 1775 to CIO 1799
12
CIO 1800 to CIO 1824
13
CIO 1825 to CIO 1849
14
CIO 1850 to CIO 1874
15
CIO 1875 to CIO 1899
Unit number
Allocated words
8
D30800 to D30899
9
D30900 to D30999
10
D31000 to D31099
11
D31100 to D31199
12
D31200 to D31299
13
D31300 to D31399
14
D31400 to D31499
15
D31500 to D31599
Section 4-1
111

Advertisement

Table of Contents
loading

This manual is also suitable for:

Sysmac cj-seriesSysmac cj1w-prm21Sysmac cs1w-prm21