Errors And Alarm Troubleshooting; Judging Errors By Indicators - Omron SYSMAC CS1W-LCB01 Operation Manual

Loop control board
Hide thumbs Also See for SYSMAC CS1W-LCB01:
Table of Contents

Advertisement

Errors and Alarm Troubleshooting

7-1

Errors and Alarm Troubleshooting

7-1-1

Judging Errors by Indicators

Indicator
Name
Color
RDY
Ready
Green
EXEC
Running
Green
COMM
Commu-
Yellow
nicating
222
RDY
EXEC
COMM
Status
Not lit
The Loop Controller is not operating for one of the following reasons:
• A Fatal Inner Board Error occurred (A40112 ON.)
• Initialization is not completed yet.
• A fatal error occurred.
• The flash memory backup data is invalid.
• The Loop Controller is initializing.
• A hardware failure occurred in the Loop Controller.
• Power is not being supplied from the Power Supply Unit.
• A Loop Controller WDT error occurred.
Flashing
• A WDT error occurred in the CPU Unit.
Lit
The Loop Controller is ready for operation.
Not lit
The system is stopped for one of the following reasons:
• The Loop Controller is initializing.
• A hardware failure occurred in the Loop Controller.
• Power is not being supplied from the Power Supply Unit.
• A Loop Controller WDT error occurred.
• The Loop Controller is not running.
• Data is being written to flash memory.
Flashing
Data is being deleted from Process-control CPU Unit (CS1D-CPU@@P)
at 0.5-s
flash memory.
intervals
Flashing
Function block data is being backed up to flash memory.
at 0.2-s
intervals
Lit
The Loop Controller is running.
Not lit
Waiting for data transfer.
Flashing
Transferring data.
Note
(1) No Loop-control CPU Unit (CJ1G-CPU@@P).
Description
Section 7-1