Omron SYSMAC CS Series Operation Manual page 159

Profibus master units
Hide thumbs Also See for SYSMAC CS Series:
Table of Contents

Advertisement

Command / Response Reference
!WARNING
Response Codes
138
PROFIBUS Ident Number (Command)
The PROFIBUS Ident Number is a 1 word identifier, issued by PROFIBUS
International, which identifies the slave device type and model. The number
can be obtained form the slave device GSD file or from the slave documenta-
tion.
New Device Address (Command)
Contains the new address of the device. The valid address range is 0 to 7E
(Hex).
Address Change Lock (Command)
Enables address lock, after changing it. Valid range:
• 00 Disable Address Lock
• 01: Enable Address Lock
Enabling Address Lock makes any future changes of the address impossible,
even after power-down/power-up of the slave device.
Response code
0000
Normal completion
1001
Command too large, i.e. > 124 words
1002
Command too short, i.e. < 4 words.
110C
• Device Address Invalid, i.e. > 7E (Hex)
• New Device Address Invalid, i.e. > 7E (Hex)
• Address change lock invalid, i.e. not equal to 00 or 01.
• Invalid target slave address (exceeds 125).
2208
PROFIBUS Master unit not in correct mode, i.e. it is in
OFFLINE mode.
0001
• The slave has deactivated this service.
• The slave has not responded to the request.
• The slave does not have sufficient memory space for the re-
quest data.
• New Address is same as current master address.
0402
Service is not supported: Device Service Access Point is
invalid.
Section 5-2