Slave New Diagnostics Flags (Word N+17 To Word N+24) - Omron SYSMAC CS Series Operation Manual

Profibus master units
Hide thumbs Also See for SYSMAC CS Series:
Table of Contents

Advertisement

Allocated CIO Area Words
Word n+9 to n+16 [n = CIO 1,500 + (25 x unit number)]]
Bit
Name
Slave
Data_Exchange
Active flags
4-2-9

Slave New Diagnostics Flags (Word n+17 to Word n+24)

Status
Controlled
by
ON
Unit
If the bit corresponding to a slave device address is ON, it indicates that
this slave device
• is allocated to the PROFIBUS Master Unit, and
• is exchanging I/O Data with PROFIBUS Master Unit.
In this case, the PROFIBUS Master Unit must be in the CLEAR mode or
the OPERATE mode.
OFF
Unit
If the bit corresponding to a slave device address is OFF, it indicates
that the slave is not in Data_Exchange with this PROFIBUS Master
Unit, due to the fact that
• the slave device is not allocated to this PROFIBUS Master Unit, or
• the slave device has been allocated to this PROFIBUS Master Unit,
but is forced out of Data_Exchange mode, due to a communication
error, or
• the slave device has been allocated to this PROFIBUS Master Unit,
but is not responding,
• the slave device has been allocated to this PROFIBUS Master Unit,
but is it has temporarily been disabled,
• the PROFIBUS Master Unit is not in CLEAR or OPERATE mode
The Slave New Diagnostics flags indicate for each slave device if it sent a new
diagnostics message to the PROFIBUS Master Unit, since the last time it was
read or cleared by the CS/CJ-series PLC. The flags are allocated to a block of
eight CIO words, and each bit in the block corresponds to a device address.
15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
Word n+17
15
14
13
12
Word n+18
31
30
29
28
Word n+19
47
46
45
44
Word n+20
63
62
61
60
Word n+21
79
78
77
76
Word n+22
95
94
93
92
Word n+23
111 110 109 108 107 106 105 104 103 102 101 100 99
Word n+24
125 124 123 122 121 120 119 118 117 116 115 114 113 112
Unit operation
11
10
9
8
7
6
5
4
27
26
25
24
23
22
21
20
43
42
41
40
39
38
37
36
59
58
57
56
55
54
53
52
75
74
73
72
71
70
69
68
91
90
89
88
87
86
85
84
Section 4-2
Slave station 00 ~ 15
3
2
1
0
Slave station 16 ~ 31
19
18
17
16
Slave station 32 ~ 47
35
34
33
32
Slave station 48 ~ 63
51
50
49
48
Slave station 64 ~ 79
67
66
65
64
Slave station 80 ~ 95
83
82
81
80
Slave station 96 ~ 111
98
97
96
Slave station 112 ~ 125
123