CX-Profibus Configurator
CS1/CJ1W-PRM21
PROFIBUS DP-V1 DTM
C200HW-PRM21 DTM
Note
SmartSlice GRT1-series
GRT1-PRT DTM
Generic Slave DTM
20
In addition to the PROFIBUS DP functions, the CS1/CJ1W-PRM21 PROFI-
BUS DP-V1 DTM provides:
• A communication channel to the user to change a remote slave device
address. This channel has its own user interface.
• Communication channels to facilitate data transfer through PROFIBUS
DP-V1 MSAC1 acyclic message transfer between a PROFIBUS DP-V1
slave device DTM and the physical slave device.
• Communication channels to facilitate data transfer through PROFIBUS
DP-V1 Class 2 acyclic message transfer between a PROFIBUS DP-V1
slave device DTM and the physical slave device. This also allows direct
connection to third-party PROFIBUS slave devices supporting PROFI-
BUS DP-V1 Class 2, e.g. PROFIBUS PA devices.
The C200HW-PRM21 DTM allows configuration of the C200HW-PRM21
PROFIBUS DP Master Unit. This predecessor of the CS1/CJ1W-PRM21 can
be used on existing C200H PLC CPU Systems as well as CS1 PLC Systems,
except for the CS1D.
The C200HW-PRM21 DTM consist of three parts:
• The Settings User Interface, which handles the settings for the C200HW-
PRM21 PROFIBUS DP Master Unit, including the bus parameters set-
tings, and the I/O data mappings.
• The Monitoring User Interface, to handle the Unit's status monitoring. The
DTM's user interface displays the Master status and Slave status.
• The communication interface between the two DTMs mentioned above
and the serial communication driver, to the C200HW-PRM21 PROFIBUS
DP Master Unit.
1. This Operation Manual does not contain a detailed description of the
C200HW-PRM21 Unit, only a description of the DTM. For more details on
the C200HW-PRM21 refer to C200H-series PROFIBUS DP Master Units
Operation Manual (W349-E2-@).
2. The C200HW-PRM21 Unit and DTM do not support PROFIBUS DP-V1.
SmartSlice GRT1-series GRT1-PRT DTM allows configuration of the GRT1-
PRT PROFIBUS Communication Unit and SmartSlice I/O Units. The DTM
provides the following user interfaces:
• The Configuration User interface to define the I/O configuration and
parameter setting for I/O data exchange with the PROFIBUS Master Unit.
• Configuration User Interfaces to configure individual SmartSlice I/O Units
attached to the GRT1-PRT.
• A monitoring User interface to monitor the status of the GRT1-PRT and
individual SmartSlice I/O Units.
The Generic Slave DTM allows the handling of classic GSD files of up to GSD
revision 3 within CX-Profibus. Upon allocating a slave device, for which only a
GSD file is available to a Master Unit in the network, this DTM will be invoked.
This DTM consists of two parts:
• The Settings User Interface will provide the user interface to display the
device's information and the selectable values, as defined in the GSD.
After making the necessary configuration settings, and saving them,
these will be transferred to the Master DTM.
• The Monitoring User Interface will provide a diagnostics interface to the
user, allowing him to check the Slave's status. This DTM obtains the nec-
essary information from the PROFIBUS Master Unit's monitoring DTM.