Basic Operating Procedure

1-5

Basic Operating Procedure

1-5-1

Overview

24
The following diagram provides an overview of the installation procedures.
For experienced installation engineers, this may provide sufficient informa-
tion. For others, cross-references are made to various sections of this manual
where more explicit information is given.
Mount the PROFIBUS Master Unit on
to the PLC
(See section 2-2 Installing the CS1/
CJ1W-PRM21 Units)
Select a unique Identity Number (0 - F)
for the Unit using the rotary switch on
the front of the Unit
(See section 2-3 Initial Setup
Procedure)
Connect the PROFIBUS Master unit to
the PROFIBUS network
(See section 2-4 Setting up a Network)
Switch on the power supply for the PLC
and create a PLC I/O table in CX-
Programmer. See CX-Programmer
User Manual (Reference No. W361).
Configure the PROFIBUS Master Unit
using CX-Profibus on the PC.
(See sections 3-3 CS1/CJ1W-PRM21
PROFIBUS Master DTM and 6-4
Configuring the Master)
Download configuration data to
PROFIBUS Master Unit.
(See sections 3-3-3 Connecting to the
CS1/CJ1W-PRM21) and 6-4-5
Downloading the Configuration)
PROFIBUS DP starts communicating,
confirmed by the COMM LED
continuously lit. Check status of other
LED Indicators (See sections 6-5 I/O
Communication Characteristics, 6-6
Operating the Network and 6-7
Monitoring the Network)