Procedures After Turning On The Power Supply; Basic Flow Of Operations; Basic Procedure - Omron E5GC User Manual

Digital temperature controllers
Hide thumbs Also See for E5GC:
Table of Contents

Advertisement

3-4
Procedures after Turning ON the
Power Supply
3-4-1

Basic Flow of Operations

The basic flow of operations after you turn ON the power supply is shown below.
3-4-2

Basic Procedure

The basic procedure is given below.
1
Turn ON the power supply.
Operation Level
2
Set the input type.
Press the O (Level) Key
for at least 3 seconds.
Press the U (Up) and
D (Down) Keys to
change the value.
When you are finished, press the O (Level) Key for at least 1 second to return to the operation display.
E5@C Digital Temperature Controllers User's Manual (H174)
1. Turn ON the power supply.
2. Set the input type.
3. Set the control method.
4. Set the alarm type.
5. Set the set point.
6. Set the alarm set values.
25
s.err
0
25
0
Initial Setting Level
in-t
5
Initial Setting Level
in-t
0
3 Part Names and Basic Procedures
s.err (input error) flashes on the display
if a sensor is not connected or if the
0
connected sensor is different from input
type. Connect a sensor if one is not
already connected.
The display flashes.
in-t (IN-T) will be displayed to show that the Initial
Setting Level has been entered.
The default setting is 5
(5: K thermocouple at −200 to 1,300 °C).
in-t (IN-T): Indicates the Input Type parameter.
Input Type: 0
(Pt100 resistance thermometer at −200 to 850 °C) (example)
3
3 - 13