Restrictions in Use of Function Blocks According to Version
Unit to monitor or set the ES100X via RS-232C communications or RS-
485 communications via RS-232C.
The following function blocks described in this manual can be used only
when Loop Control Unit CS1W-LC001 Ver.1.20 and onwards and CX-
Process Tool Ver.1.20 and onwards are used:
Á
The following function blocks can be registered on CX-Process Tool
when Loop Control Unit Ver.1.0
onwards are used. However, if the data of these function blocks is
downloaded to the Loop Control Unit in major item units (units of Loop
Control Unit) when these function blocks are registered on CX-Process
Tool, an error occurs, and the download is canceled. (Other function
blocks also are not downloaded.)
Á
The following function blocks cannot be registered on CX-Process Tool
when Loop Control Unit Ver.1.20 and onwards and CX-Process Tool
Ver.1.00 are used. For this reason, these function blocks cannot also be
downloaded to the Loop Control Unit.
If the following function blocks already exist on the Loop Control Unit and
are uploaded to CX-Process Tool, only the following function blocks are
not uploaded. (When a new upload is performed, these blocks become
empty.)
2-position ON/OFF (Block Model 001), 3-position ON/OFF (Block Model 002),
Blended PID (Block Model 013), 3-input Selector (Block Model 163), 3-output
Selector (Block Model 164), Batch Data Collector (Block Model 174), DI
Terminal from Expanded CPU Unit (Block Model 455), DO Terminal from
Expanded CPU Unit (Block Model 456), AI Terminal from Expanded CPU
Unit (Block Model 457), AO Terminal from Expanded CPU Unit (Block Model
458)
Note
The version of the Loop Control Unit can be verified in the Monitor run status
screen ([Execute]-[Run]-[Monitor run status]) on CX-Process Tool.
When the above function blocks are used, check in the Check System
Operation screen on CX-Process Tool beforehand that the content of ITEM
099 onwards in the System Common block (Block Model 000) is as follows.
ITEM
099
The following function blocks described in this manual can be used only
when Loop Control Unit CS1W-LC001 Ver.1.50 and onwards and CX-
Process Tool Ver.1.50 and onwards are used:
Á
The following function blocks can be registered on CX-Process Tool
when versions of Loop Control Unit earlier than Ver.1.50 (Ver.1.0
Ver.1.20) and CX-Process Tool Ver1.50 or onwards are used. However,
if the data of these function blocks is downloaded to the Loop Control
Unit in major item units (units of Loop Control Unit) when these function
blocks are registered on CX-Process Tool, an error occurs, and only
those function blocks are not downloaded. (Other function blocks are
downloaded successfully.)
Á
The following function blocks cannot be registered on CX-Process Tool
when Loop Control Unit Ver.1.50 and onwards and versions of CX-
Data name
MPU/FROM version indication
Version V1.20 and onwards must be indicated.
and CX-Process Tool Ver1.20 or
Data
V1.20V1.20
or
xiii