Omron CS1W-LC001 Operation Manual page 34

Loop control unit
Table of Contents

Advertisement

Outline
Example 1
Example 2
Example 3
14
Field Term inal
block
Analog
input
Field Term inal
block
Analog
input
 The Loop Control Unit handles analog I/O signals not in engineering units
but in percentage units.
At analog input, the converted values 0000 to 0FA0 (FF38 to 1068) Hex from
the Analog Input Unit for input 4 to 20 mA (3.2 to 20.8 mA) are converted to
0.00 to 100.00% (-5.00 to 105.00%) before they are processed by the Loop
Control Unit.
At analog input, the converted values F830 to 07D0 (F768 to 0898) Hex from
the Analog Input Unit for input -10 to +10 mV (-11 to +11 V) are converted to
0.00 to 100.00% (-5.00 to 105.00%) before they are processed by the Loop
Control Unit.
At analog output, the values 0.00 to 100.00% (-5.00 to 105.00%) are
converted to setting values 0000 to 0FA0 (FF38 to 1068) Hex before 4 to 20
mA (3.2 to 20.8 mA) is output from the Analog Output Unit.
Note
Converted values (in the case of analog input) for 0 to 100% on the Loop
Control Unit and setting values (in the case of analog output) for 0 to 100%
on the Loop Control Unit are fixed to the same values as the user ranges.
However, in the case of isolated-type Analog Input Units (CS1W-
PTS01/02/03, PTW01, PDC01, PPS01, PTR01), the Analog Input Unit itself
has a range setting function. So, any values can be specified as the
converted values (on condition that the same setting as the range setting is
made).
Software wiring
Operation block
Control block
Addition/
Subtraction
Field Term inal block
PID
Analog
output
Param eters
ITEM
Data
000
001
002
:
:
Section
1-1