Basic Examples of PID Control
5-1-7

Monitoring and Accumulating Flowrate

Block address
160
Function blocks used: PI 4-point Terminal (Block Model 562)
Connect the instantaneous value output value of the PI 4-point Terminal
block to the Accumulator for instantaneous value input block when
accumulating 8-digit accumulated values based on the instantaneous values
from the Pulse Input Unit CS1W-PPS01.
Example
Pulse input
ITEM No.
901
002
010
021
100
002
007
008
009
010
012
013
Note 1
This instantaneous value differs from the instantaneous value, that is
reflected in the allocated relay words n+1 to n+4 of the Pulse Input Unit
CS1W-PPS01, in that the instantaneous value is for each operation cycle of
the PI 4-point Terminal block.
Accumulator for instantaneous value input (Block
Model 150)
Let's apply scaling of 0 to 6000 to zero (0%) through to span
(100%) of the pulsse input instantaneous value, and set
accumulation to maximum 1200.00 per hour. (The accumulated
value is taken to be 1200.00 when 6000 has continued for 100%
for one hour.) The accumulation result is stored to ITEM012 and
ITEM013 of the Accumulator for instantaneous value input block.
PI 4-point
Terminal
Block Model 562
Data
562
PI 4-point terminal block
3
Instantaneous value output range 3: 0 to 6000
0 to
Y1 (instantaneous value output value 1) Note 1
115.00%
150
Accumulator for instantaneous value input
901021
X1 source designation
Input
1200.00
QR accumulation rate (accumulation value when input
100% is continuous for one hour)
2
TU time unit (2: time)
0000 to
Accumulated value (lower 4 digits)
9999
0000 to
Accumulated value (upper 4 digits)
9999
Section
Instantaneous
Accumulator for
value
instantaneous
value input
Block Model 150
Explanation
5-1