Configuration of Function Blocks
Connecting via the Step Ladder Program block
Example
Connecting via the Contact Distributor block
Example
82
When logical operation is required, use the Step Ladder Program block
(Block Model 301).
Input ITEM086 (Auto/Manual switch) of the Basic PID block of block address
001, and output ITEM086 reflected in ITEM026 (Remote/Local switch) of the
Basic PID block of block address 002.
Block address: 001
Basic PID
block
086
011
A/M
When logical operation is not required, use the Contact Distributor block
(Block Model 201).
Input ITEM014 (High PV alarm) of the Basic PID block of block address 001,
and write ITEM014 to ITEM021 (A1 selection command) of the Constant
Selector block (Block Model 165) of block address 100.
Block address: 001
Basic PID
block
014
High PV alarm
Block address: 400
Step Ladder
Program block
012
001-086
002-026
A/M
R/L
Block address: 400
ITEM number
Command code
Command
011
LOAD
01
012
OUT NOT
12
Block address: 101
Contact Distributor
block
007
008
Source
Destination
designation (S1)
designation (E1)
Block address: 101
ITEM number
Data
007
001014
008
100021
Section
Block address: 002
Basic PID
block
026
Remote/Local sw itch
Operand
001086
002026
Block address: 100
Contact
Selector block
021
A1 selection command
3-1