Omron CS1W-LC001 Operation Manual page 150

Loop control unit
Table of Contents

Advertisement

Exchanging Data with CX-Process Monitor/SCADA Software and with Other Nodes Section
Record number
Function block file name
LCU name
Tag No. (representative tag)
Tag TEM
Tag comment
Tag type
Data attribute
Contact alarm tag
Scaling upper limit
Scaling lower limit
Decimal point position (for scaling)
Unit
Data range upper limit
Data range lower limit
Network address
Node address
Unit address
I/O memory area
I/O memory address
Bit position
Function block face plate (same as
block model)
Block address
ITEM number
Offset (write data)
Read/write
3-4-4
Exchanging Data with a Loop Control Unit at Other Node
132
The contents of a CSV tag file is shown below.
Contents
You can select the following two modes for exchanging data with a Loop
Control Unit at another node via the Controller Link.
1) To use part of the regular Data Link (use the CPU Unit Terminal
block or Expanded CPU Unit Terminal block)
Use this mode when exchanging data with a PC (CPU Unit) at another node
or when exchanging data with a Loop Control Unit at the other node PC.
Note
The maximum number of points must be within the "number of points used by
the CPU Unit Terminal (maximum number of function blocks 16, 128 contacts
per function block, analog value eight words) + number of points used by the
Expanded CPU Unit Terminal block (maximum number of function blocks 30,
64 contacts per function block, analog value 64 words)".
The regular Controller Link Data Link with the PC at the other node is
established on the PC on which the Loop Control Unit is mounted. On this
Data Link, the Loop Control Unit reads and writes the analog signals or
contact signals to part of the Data Link on the CPU Unit by the CPU Unit
Terminal block or Expanded CPU Unit Terminal block. Reading and writing in
Setting range
1 to 65535
Max. 6 characters
Max. 6 characters
Max. 16 characters (Unusable characters: None)
Fixed for each function block item
Max. 16 characters (Unusable characters: None)
0: Analog, 1: Contact
Analog
0: Default, 1: Unit, 2: Integer
Contact
0: OFF, 1: ON, 2: COS, 3: COSON
0: Normal, 1: Alarm
5000 to 99999
(Example for DP position of 1: -550.0 to 9999.9)
5000 to 99999
(Example for DP position of 1: -550.0 to 9999.9)
0 to 9
Max. 8 characters (Unusable characters: None)
5000 to 99999
5000 to 99999
0 to 127
1 to 32
16 to 31
0: CIO, 1: W, 2: H, 3: D, 4: E0
0 to 65535
0 to 15
0 to 999
0 to 999
0 to 999
32767
0: Same address for read and write, Not 0: Read
address + offset
R: Read, RW: Read/write, W: Write
3-4