Exchanging Data with CX-Process Monitor/SCADA Software and with Other Nodes Section
Example
AI 4-point
Block Model
586
AO 4-point
Block Model
587
Example
1-Block Send Terminal to Computer
1) Specify the source designation of function block or analog/contact signal
by the Send to Computer blocks
(1) Specify the function block to be monitored or set by CX-Process Monitor
by the 1-Block Send Terminal to Computer block (Block Model 403) or 4-
Block Send Terminal to Computer block (Block Model 404) as the source
designation.
(2) Specify the analog signals (including parameters) to be monitored by CX-
Process Monitor by the AO to Computer (Block Model 402) as the source
designation.
(3) Specify the contact signals (including parameters) to be monitored by
CX-Process Monitor by the DO to Computer (Block Model 401) as the
source designation.
(4) Register the AO Terminal Settings from Computer block (Block Model
410) or DO Terminal Settings from Computer block (Block Model 409) to
be monitored or set by CX-Process Monitor. (The re-issue to network
ITEM must be set to ON.)
PV1
Square Root
Block Model
131
2) Set the tag number for function blocks or analog/contact signals
(including parameters).
CPU Unit I/O Memory, Data
Memory (D) Area
Block Model 403
1-Block Send Terminal to Computer
Block Model 403
3) Compile a log data file by CX-Process Tool running on Windows NT.
1-Block Send Terminal to Computer
Block Model 403
Send
command
Basic PID
MV1
Block Model 011
Send
command
RSP
Basic PID
PV2
Block Model 011
Area to send to
Send
computer in Data
Memory (D) for Node
Terminals
Send
CPU Unit I/O Memory, Data
Memory (D) Area
1-Block Send Terminal to Computer
Block Model 403
MV2
CX-Process Monitor
Reading of specified tag number
3-4
Area to send to
Send
computer in Data
Memory (D) for
Node Terminals
Send
127