Basic Procedure for Using the Loop Control Unit
4. Downloading the function block data to the Loop Control Unit
Refer to the Programming Devices (CX-Programmer or Programming
Console) Operation Manual.
6) If necessary, set the communications conditions of the serial
communications port in the PC Setup using the Programming Devices.
Refer to the Programming Devices (CX-Programmer or Programming
Console) Operation Manual.
7) Set the allocated Data Memory (D) on the Analog Input and Output Units
using the Programming Devices.
Refer to the Analog Input and Output Unit manuals.
1) Turn power OFF to the PC.
2) Set the unit number setting switch on the front panel of the CPU Unit.
Refer to the CS1 PC Operation Manual.
3) Connect the CPU Unit to the computer on which CX-Process Tool is
running.
4) Turn the PC ON.
5) Set the network address (000), node address (01) and unit address (unit
number + 10 Hex in decimal).
Refer to the CX-Process Tool Operation Manual.
6) Perform the Host Link connection operation on CX-Process Tool ([File]-
[Initialize Serial Port]).
Refer to the CX-Process Tool Operation Manual.
7) Download the function block data to the Loop Control Unit specified in the
Function Block Data Sheet of CX-Process Tool ([Execute]-[Download]).
Refer to the CX-Process Tool Operation Manual.
Loop Control Unit
CPU Unit
Peripheral port or RS-232C port
Prepare function block data on
CX-Process Tool on the
computer.
Function block
data
Section
1-5
55