Omron CS1W-LC001 Operation Manual page 226

Loop control unit
Table of Contents

Advertisement

How to Use the Step Ladder Program Block
Command
Command
code
Â
Draw line
Â
Delete line
Â
END
00
Â
NO
30
OPERATION
Note 1
The ON signal for one operation cycle that is generated by the differentiate up (DIFU) or
differentiate down (DIFD) command automatically turns OFF at the start of the Step Ladder
Program block of the next operation cycle. (This signal does not turn OFF by the DIFU or DIFD
command in the Step Ladder Program.)
Á
Note 2
When the ON signal for one operation cycle that is generated by the DIFU or DIFD command
is used by another function block, set the operation cycle to the same or higher than the
operation cycle of the Step Ladder Program. The ON signal sometimes cannot be read
normally when an operation cycle that is lower than the operation cycle of the Step Ladder
Program is set.
Á
A contact ITEM that has been turned ON by the OUT command stays ON even if program
execution moves to the next STEP. For this reason, to perform step progression control in a
step sequence, use the RESET command at the next STEP to turn OFF the contact ITEM that
has been turned ON.
Ladder symbol
Operand
ED
NP
Description
Connects vertical or
horizontal lines.
Deletes vertical or
horizontal lines.
Indicates the end of a
program.
Note: The END
instruction is
automatically
placed at the end
of program when
the Step Ladder
Program block is
prepared using
CX-Process Tool.
It is placed after
STEP00 when the
program comprises
STEP00 only, and
is placed after the
nth STEP where
the program ends.
This instruction has no
function. (No processing
is performed for NOP.)
Appendix 1
: Can be used
Á
: Cannot be used
Input
conditions In logic
sequence
Â
Â
Not required
Not required
In step
sequence
209

Advertisement

Table of Contents
loading

Table of Contents