Simple Example of Use
When using the CX-Process Monitor
6. Set the Terminals to Computer for CX-Process Monitor.
On CX-Process Tool, specify the two Basic PID blocks that are to be
monitored by CX-Process Monitor as the source designation of the 1-
Block Send Terminal to Computer block (Block Model 403)*1.
Â
1: The PID blocks cannot be registered to the Tuning screen by 4-Block
Send Terminal to Computer block (Block Model 404).
Note
Only the Control blocks and some of the Operation blocks (in case of 4-Block
Send Terminal blocks) can be sent as the function blocks to CX-Process
Monitor by the 1-Block Send Terminal to Computer block or 4-Block Send
Terminal to Computer block. The ITEMs in each of these function blocks are
also predetermined as defaults. (A fixed name called a "tag ITEM" is
allocated to each ITEM.) To send ITEMs other than these (such as contacts
or analog value parameters) to CX-Process Monitor, specify that ITEM as the
source designation by the DO to Computer block or the AO to Computer
block.
7. Set the monitor tags.
Set the tag number, tag comment, scaling, unit and decimal point position
on CX-Process Tool.
By setting the tag number set here on CX-Process Monitor, you can
monitor function blocks sent by the Send to Computer blocks, analog
signals (including parameters) and contact signals (including parameters).