Closed-Loop Field Current Control, Field Gating Unit; P250 Alpha G Limit (Field); P251 Alpha W Limit (Field); P252 Filtering Of Line Frequency Correction (Field) - Siemens 6RA70 Series Instructions Manual

Microprocessor-based converters from 15a to 1680a for variable speed dc drives
Hide thumbs Also See for 6RA70 Series:
  • Faq (4 pages)
Table of Contents

Advertisement

PNU
Description
P229
Control of I component tracking for slave drive
*
0
On a slave drive, the I component of the speed controller is
FDS
made to follow such that M(set, ncontr.) = M(set, limit),
the speed setpoint is set to the actual speed value
(G152)
1
Tracking deactivated
P230
Setting period of speed controller integrator
After a positive edge at the binector set in P695, the integrator of the speed
FDS
controller is set to the instantaneous value of the connector set in P631.
If a time of > 0 is set on P230, this setting operation is not performed just
(G152)
once, but the speed controller integrator is set continually to the setting
value for the parameterized time period.
P234
Set speed controller P component to zero
*
0
Set controller P component to zero (i.e. to obtain a pure I
FDS
controller)
(G152)
1
Controller P component is active
P236
Specifying the dynamic response of the speed control loop
*
FDS
The parameter value is used as the optimization criterion for the speed
control loop.
Note:
Changes to this value do not take effect until the speed controller
optimization run (P051 = 26, see Section 7.5) has been executed.
Setting instructions:
For drives, for example, with gear backlash, optimization should be
-
started with low dynamic response values (from 10%).
For drives with top synchronism and dynamic response requirements,
-
values up to 100% should be used.

10.12 Closed-loop field current control, field gating unit

P250
Alpha G limit (field)
FDS
Rectifier stability limit for firing angle of field converter
(G166)
P251
Alpha W limit (field)
FDS
Inverter stability limit for firing angle of field converter
(G166)
P252
Filtering of line frequency correction (field)
*
The internal line synchronization for the field gating pulses derived from the
FDS
field mains infeed terminals is filtered with this time constant. In operation
on "weak" power supplies with unstable frequencies, for example, on a
(G166)
diesel-driven generator (isolated operation), the filter time constant must be
set lower than for operation on "constant V/Hz" systems in order to achieve
a higher frequency correction speed.
Using the units position, the line synchronization function can be altered
additionally as follows:
When the parameter is set to an uneven number, the measured line zero
crossings for line synchronization are subjected to an extra "filter", may
improve performance in the case of difficulties with brief mains interruptions
(e.g. power supply via sliding current collectors), but may only be set for
constant V/Hz power supplies (not for weak isolated supply systems).
P253
Control word for field precontrol
*
0
Field precontrol disabled, precontrol output = 180°
FDS
1
Field precontrol active, output is dependent on field current
(G166)
setpoint, field line voltage, P112
P254
Set field current controller I component to zero
*
0
Set controller I component to zero (i.e. to obtain pure P
FDS
controller)
(G166)
1
Controller I component is active
P255
Field current controller P gain
FDS
This parameter is set automatically during the optimization run for precontrol
(G166)
and current controller (armature and field) (P051=25).
10-36
Value range
[Unit]
Steps
0 to 1
1
[SW 1.9 and later]
0 to 10000
[ms]
1ms
0 to 1
1
10 to 100
[%]
[SW 2.0 and later]
1
0 to 180
[degrees]
1 degree
0 to 180
[degrees]
1 degree
0 to 200
[ms]
1ms
0 to 1
1
0 to 1
1
0.01 to 100.00
0.01
SIMOREG DC Master Base Drive Panel Operating Instructions
No. indices
See
Factory
Change
setting
(Access /
Type
Status)
Ind: 4
P052 = 3
FS=0
P051 = 40
Type: O2
Offline
Ind: 4
P052 = 3
FS=0
P051 = 40
Type: O2
on-line
Ind: 4
P052 = 3
FS=1
P051 = 40
Type: O2
Offline
Ind: 4
P052 = 3
FS=75
P051 = 40
Type: O2
online
Ind: 4
P052 = 3
FS=0
P051 = 40
Type: O2
Online
Ind: 4
P052 = 3
FS=180
P051 = 40
Type: O2
Online
Ind: 4
P052 = 3
FS=200
P051 = 40
Type: O2
Offline
Ind: 4
P052 = 3
FS=1
P051 = 40
Type: O2
Offline
Ind: 4
P052 = 3
FS=1
P051 = 40
Type: O2
Offline
Ind: 4
P052 = 3
FS=5.00
P051 = 40
Type: O2
Online
SIEMENS Energy & Automation