Access Authorization Levels; P051 Key Parameters; P052 Selection Of Display Parameters; P050 Language - Siemens 6RA70 Series Instructions Manual

Microprocessor-based converters from 15a to 1680a for variable speed dc drives
Hide thumbs Also See for 6RA70 Series:
  • Faq (4 pages)
Table of Contents

Advertisement

PNU
Description
P046
Binector display:
*
i001:
Selection of binector displayed in r045.01
i002:
Selection of binector displayed in r045.02
(G121)
i003:
Selection of binector displayed in r045.03
i004:
Selection of binector displayed in r045.04
r047
Display of fault diagnostic memory
Provides more detailed information about the cause of a fault after activation
of a fault message (see Section 10).
i001
Word 1 (fault value)
i002
Word 2
...
i016
Word 16 (fault number)
r048
Hours run
Display of time (hours) in which drive has been operating in states I, II or - -.
(G189)
All times of ≥ approx. 0.1 s are included in the count.
r049
Fault time
Display of time at which the current fault, and the last 7 acknowledged
(G189)
faults, were activated.
i001:
Current fault
st
i002:
1
acknowledged fault
nd
i003:
2
acknowledged fault
rd
i004:
3
acknowledged fault
th
i005:
4
acknowledged fault
th
i006:
5
acknowledged fault
th
i007:
6
acknowledged fault
th
i008:
7
acknowledged fault
P050
Language
*
Language of plaintext display on optional OP1S operator panel and in
DriveMonitor PC service routine
0:
German
1:
English
2:
Spanish
3:
French
4:
Italian
10.3

Access authorization levels

P051
Key parameters
*
0
No access authorization
6
Do not set (for use by DriveMonitor)
7
Do not set (for use by DriveMonitor)
9
Do not set (for use by DriveMonitor)
21
Restore factory settings
All parameters are reset to their defaults (factory settings).
Parameter P051 is then automatically reset to factory setting
"40".
22
Execute internal offset compensation (see Section 7.4)
25
Optimization run for precontrol and current controller (armature
and field) (see Section 7.5)
26
Optimization run for speed controller (see Section 7.5)
27
Optimization run for field weakening (see Section 7.5)
28
Optimization run for compensation of friction and moment of
inertia (see Section 7.5)
29
Optimization run for the speed controller with an oscillating
mechanical system (see Section 7.5)
40
Access authorization to parameter values for authorized service
personnel
P052
Selection of display parameters
*
0
0
Display only parameters that are not set to original factory
settings
1
Display only parameters for simple applications
3
Display all parameters used
SIEMENS Energy & Automation
SIMOREG DC Master Base Drive Panel Operating Instructions
hours
hours
hours
hours
hours
hours
hours
hours
Value range
No. indices
[Unit]
Factory
Steps
setting
Type
All binector numbers
Ind: 4
1
FS=0
Type: L2
0 to 65535
Ind: 16
1
Type: O2
0 to 65535
Ind: None
[hours]
Type: O2
1 hour
0 to 65535
Ind: 8
[hours]
Type: O2
1 hour
0 to 4
Ind: None
1
FS=0
Type: O2
see column on left
Ind: None
FS=40
Type: O2
0, 1, 3
Ind: None
FS=3
Type: O2
See
Change
(Access /
Status)
P052 = 3
P051 = 40
Online
P052 = 3
P052 = 3
P052 = 3
P052 = 3
P051 ≥ 0
Online
P052 = 3
P051 ≥ 0
Online
P052 = 3
P051 ≥ 0
Online
10-11