PNU
Description
r064
Board compatibility
Compatibility identifier of boards in locations 1 to 3 of electronics box.
(G101)
The compatibility identifier is bit-coded. To ensure the compatibility of a
board, it must have a "1" setting at the same bit location of the parameter
value as the CUD (in location 1 / index i001).
Indices:
i001:
Compatibility identifier of board in location 1
i002:
Compatibility identifier of board in slot D
i003:
Compatibility identifier of board in slot E
i004:
Compatibility identifier of board in slot F
i005:
Compatibility identifier of board in slot G
Example:
Index Value
Bit representation
i001
253
0000 0000 1111 1101
i002
002
0000 0000 0000 0010
i003
001
0000 0000 0000 0001
r065
Software identifiers
Extended software version identifiers in locations 1, 2, and 3 of the
(G101)
electronics box
Indices:
i001:
Software identifier of the board in location 1
i002:
Software identifier of the board in slot D
i003:
Software identifier of the board in slot E
i004:
Software identifier of the board in slot F
i005:
Software identifier of the board in slot G
P067
Load class
*
1
Load class DC I
2
Load class DC II
(G101)
3
Load class DC III
4
Load class DC IV
5
US rating
The load classes are described in Chapter 3.4.1.
Depending on the load class selected, the device rated DC of the
SIMOREG DC Master is reduced to a value of different magnitude to suit
the power section and load class.
The current value of the device rated DC is indicated in parameter r072.002.
Notes:
If the device rated DC is reduced via parameter P076.001, the lesser of the
two values is active.
If you set a value of > 1 in P067, you must ensure that the "Dynamic
overload capability of power module" is enabled, i.e. a value of > 0 must be
set in parameter P075.
The SIMOREG DC Master does not monitor for compliance with the criteria
of the load class set in parameter P067. If permitted by the power module,
the unit can operate for overload periods in excess of those defined by the
load class. The permissible overload period for the installed power module
is always longer than the period defined for the load class. The SIMOREG
DC Master does monitor the actual permissible overload period for the
power module. See Section 9.15.
r068
Options according to rating plate
0
No option
(G101)
1
Option L04 (low voltage, 85V)
2
Option K00 (terminal expansion)
3
L04 and K00
10-14
Compatible with CUD
no
yes
[SW1.8 and later]
SIMOREG DC Master Base Drive Panel Operating Instructions
Value range
No. indices
[Unit]
Factory
Steps
setting
Type
Ind: 5
Type: O2
Ind: 5
Type: O2
1 to 5
Ind: None
1
FS=1
Type: O2
Ind: None
Type: 02
SIEMENS Energy & Automation
See
Change
(Access /
Status)
P052 = 3
P052 = 3
P052 = 3
P051 = 40
off-line
P052 = 3

Advertisement

Table of Contents
loading

Table of Contents