External Faults - Siemens 6RA70 Series Instructions Manual

Microprocessor-based converters from 15a to 1680a for variable speed dc drives
Hide thumbs Also See for 6RA70 Series:
  • Faq (4 pages)
Table of Contents

Advertisement

Fault
No.
Cause as a function of fault value
(r047.001, r949.001 or r949.009 with acknowledged error)
F015
Telegram failure on one SIMOLINK board
(active when U741 > 0 as soon as the first valid telegram is received)
After receipt of one valid telegram, no further valid telegrams have arrived within the period set in parameter U741.
Possible fault causes
♦ Break in connecting cable
♦ Parameter setting change during telegram exchange (for parameters see Section 11 "Configuration of SIMOLINK board)
♦ U741 is set to low
Fault value:
1 Telegram failure on 1
2 Reserved
F016
Hardware fault on expansion board EB1
Fault value:
1
Fault on first EB1
2
Fault on second EB1
F017
Hardware fault on expansion board EB2
Fault value:
1
Fault on first EB2
2
Fault on second EB2
F018
Short circuit or overloading of binary outputs
(active in all operating states)
Possible fault causes
♦ Short circuit or overload at terminals 46, 48, 50 or 52 and 26 or 34
Fault value:
1
Short circuit or overload at binary outputs
NOTICE
This monitoring function is deactivated in the delivery state. It can be activated via parameter P820.
9.1.2.3

External faults

F019
Fault message from free function block FB286
(active in all operating states)
Fault value:
1
the binector wired via parameter U100 Index.005 is in the state log."1"
2
the binector wired via parameter U100 Index.006 is in the state log."1"
3
the binector wired via parameter U100 Index.007 is in the state log."1"
4
the binector wired via parameter U100 Index.008 is in the state log."1"
F020
Fault message from free function block FB287
(active in all operating states)
Fault value:
1
the binector wired via parameter U101 Index.005 is in the state log."1"
2
the binector wired via parameter U101 Index.006 is in the state log."1"
3
the binector wired via parameter U101 Index.007 is in the state log."1"
4
the binector wired via parameter U101 Index.008 is in the state log."1"
Siemens Energy & Automation
SIMOREG DC Master Base Drive Panel Operating Instructions
st
SLB
Description
Further information (r047.002 to r047.016)
r047 Index 002 to 016:
i002 Bit 8 = 1:
Overload at terminal 46
Bit 9 = 1:
Overload at terminal 48
Bit 10 = 1: Overload at terminal 50
Bit 11 = 1: Overload at terminal 52
Bit 12 = 1: Overload at terminal 26 (15 V output)
Bit 13 = 1: Overload at terminal 34, 44 and/or 210
(24 V output)
9-7

Advertisement

Table of Contents
loading

Table of Contents