P492 Analog Monitoring Of Motor Temperature: Trip Temperature; P495 Brush Length Sensing: Tripping Of Alarm Or Fault Message; P496 Bearing Condition: Tripping Of Alarm Or Fault Message; P497 Air Flow: Tripping Of Alarm Or Fault Message - Siemens 6RA70 Series Instructions Manual

Microprocessor-based converters from 15a to 1680a for variable speed dc drives
Hide thumbs Also See for 6RA70 Series:
  • Faq (4 pages)
Table of Contents

Advertisement

PNU
Description
P492
Analog monitoring of motor temperature: Trip temperature
FDS
Operative only when P490.x=1.
(G185)
P493
Motor temperature analog 1 (temperature sensor at terminals 22 / 23):
*
Tripping of alarm or fault message
FDS
Motor temperature grasped with KTY84
(G185)
0
Monitoring deactivated
1
Alarm (A029) at temperature > P491
2
Fault message (F029) at temperature > P492
3
Alarm (A029) at temperature > P491 and
fault message (F029) at temperature > P492
Motor temperature grasped with PTC thermistor
0
Monitoring deactivated
1
Alarm message (A029) when operating point of PTC thermistor
is reached
2
Fault message (F029) when operating point of PTC thermistor is
reached
3
Illegal setting
P494
Motor temperature analog 2 (temperature sensor at terminals 204 /
*
205): Tripping of alarm or fault message
FDS
Motor temperature grasped with KTY84
0
Monitoring deactivated
(G185)
1
Alarm (A029) at temperature > P491
2
Fault message (F029) at temperature > P492
3
Alarm (A029) at temperature > P491 and
fault message (F029) at temperature > P492
Motor temperature grasped with PTC thermistor
0
Monitoring deactivated
1
Alarm message (A029) when operating point of PTC thermistor
is reached
2
Fault message (F029) when operating point of PTC thermistor is
reached
3
Illegal setting
P495
Brush length sensing: Tripping of alarm or fault message
*
0
No brush length sensing (terminal 211 is not scanned)
FDS
1
Binary brush length sensing (terminal 211 is scanned)
Alarm (A025) in response to 0 signal
(G186)
2
Binary brush length sensing (terminal 211 is scanned)
Fault message (F025) in response to 0 signal
P496
Bearing condition: Tripping of alarm or fault message
*
0
No bearing condition sensing (terminal 212 is not scanned)
FDS
1
Bearing condition sensing (terminal 212 is scanned)
Alarm (A026) in response to 1 signal
(G186)
2
Bearing condition sensing (terminal 212 is scanned)
Fault message (F026) in response to 1 signal
P497
Air flow: Tripping of alarm or fault message
*
0
No air flow monitoring (terminal 213 is not scanned)
FDS
1
Air flow monitoring (terminal 213 is scanned)
Alarm (A027) in response to 0 signal
(G186)
2
Air flow monitoring (terminal 213 is scanned)
Fault message (F027) in response to 0 signal
P498
Temperature switch: Tripping of alarm or fault message
*
0
No temperature switch connected (terminal 214 is not scanned)
FDS
1
Temperature switch connected (terminal 214 is scanned)
Alarm (A028) in response to 0 signal
(G186)
2
Temperature switch connected (terminal 214 is scanned)
Fault message (F028) in response to 0 signal
10-52
Value range
[Unit]
Steps
0 to 200
[°C]
1°C
0 to 3
1
0 to 3
1
0 to 2
1
0 to 2
1
0 to 2
1
0 to 2
1
SIEMENS Energy & Automation
SIMOREG DC Master Base Drive Panel Operating Instructions
No. indices
See
Factory
Change
setting
(Access /
Type
Status)
Ind: 4
P052 = 3
FS=0
P051 = 40
Type: O2
Online
Ind: 4
P052 = 3
FS=0
P051 = 40
Type: O2
Offline
Ind: 4
P052 = 3
FS=0
P051 = 40
Type: O2
Offline
Ind: 4
P052 = 3
FS=0
P051 = 40
Type: O2
Offline
Ind: 4
P052 = 3
FS=0
P051 = 40
Type: O2
Offline
Ind: 4
P052 = 3
FS=0
P051 = 40
Type: O2
Offline
Ind: 4
P052 = 3
FS=0
P051 = 40
Type: O2
Offline

Advertisement

Table of Contents
loading

Table of Contents