10.23 Connector selector switches

(see also Section 8, Function Diagram Sheet G124 of Operating Instructions 6RX1700-0AD**)
P455
Source for inputs of connector selector switch 1
*
Selection of connectors for the input signals for connector selector switch 1.
(G124)
0 = connector K0000
1 = connector K0001
etc.
P456
Source for control of connector selector switch 1
*
Selection of binectors to control connector selector switch 1.
(G124)
0 = binector B0000
1 = binector B0001
etc.
P457
Source for inputs of connector selector switch 2
*
Selection of connectors for the input signals for connector selector switch 2.
(G124)
0 = connector K0000
1 = connector K0001
etc.
P458
Source for control of connector selector switch 2
*
Selection of binectors to control connector selector switch 2.
(G124)
0 = binector B0000
1 = binector B0001
etc.

10.24 Motorized potentiometer

(see also Section 8, Sheet G126 of Operating Instructions 6RX1700-0AD**)
P460
Control word for motorized potentiometer ramp-function generator
*
0
The motorized potentiometer ramp generator is bypassed in
FDS
Automatic mode (same effect as for P462 and P463 = 0.01, i.e.
the generator output is made to follow the automatic setpoint
(G126)
without delay)
1
Motorized potentiometer ramp generator is active in Manual and
Automatic modes
P461
Source for setpoint in Automatic mode
*
Selection of the connector to be applied as the Automatic setpoint to the
FDS
ramp-function generator in the motorized potentiometer
(G126)
0 = connector K0000
1 = connector K0001
etc.
P462
Ramp-up time for motorized potentiometer
FDS
(G126)
P463
Ramp-down time for motorized potentiometer
FDS
(G126)
SIEMENS Energy & Automation
SIMOREG DC Master Base Drive Panel Operating Instructions
Value range
[Unit]
Steps
[SW 1.9 and later]
All binector numbers
1
All connector
[SW 1.9 and later]
numbers
1
All binector numbers
[SW 1.9 and later]
1
[SW 1.9 and later]
All connector
numbers
1
[SW 1.9 and later]
All binector numbers
1
0 to 1
1
All connector
numbers
1
0.01 to 300.00
[s]
0.01s
0.01 to 300.00
[s]
0.01s
No. indices
See
Factory
Change
setting
(Access /
Type
Status)
Ind: 2
P052 = 3
FS=1
P051 = 40
Type: L2
off-line
Ind: 3
P052 = 3
FS=0
P051 = 40
Type: L2
off-line
Ind: 2
P052 = 3
FS=0
P051 = 40
Type: L2
off-line
Ind: 3
P052 = 3
FS=0
P051 = 40
Type: L2
off-line
Ind: 2
P052 = 3
FS=0
P051 = 40
Type: L2
off-line
Ind: 4
P052 = 3
FS=1
P051 = 40
Type: O2
Offline
Ind: 4
P052 = 3
FS=0
P051 = 40
Type: L2
Offline
Ind: 4
P052 = 3
FS=10.00
P051 = 40
Type: O2
Online
Ind: 4
P052 = 3
FS=10.00
P051 = 40
Type: O2
Online