Drive Faults; F030 Commutation Failure Or Overcurrent Has Occurred (Active In Operating States Of – –, I, Ii); F033 Fault Message From Free Function Block Fb4 (Active In All Operating States); F029 Motor Overtemperature (Active In All Operating States) - Siemens 6RA70 Series Instructions Manual

Microprocessor-based converters from 15a to 1680a for variable speed dc drives
Hide thumbs Also See for 6RA70 Series:
  • Faq (4 pages)
Table of Contents

Advertisement

Fault
No.
Cause as a function of fault value
(r047.001, r949.001 or r949.009 with acknowledged error)
F029
Motor overtemperature
(active in all operating states)
Select via
P493=2 or 3 (temperature sensor at terminals 22 / 23) or
P494=2 or 3 (temperature sensor at terminals 204 / 205)
When parameter P490.01=1 (KTY84 at terminals 22 / 23) or P490.02=1 (KTY84 at terminals 204 / 205):
The fault message is activated if the motor temperature reaches or exceeds the value set in parameter P492.
When parameter P490.01=2, 3, 4 or 5 (PTC thermistor at terminals 22 / 23) or P490.02=2, 3, 4 or 5 (PTC thermistor at terminals
204/ 205):
The fault message is activated if the motor temperature reaches or exceeds the response value of the selected PTC thermistor.
Fault value:
1
Fault activation through temperature sensor at terminals 22 / 23
2
Fault activation through temperature sensor at terminals 204 / 205
9.1.2.5

Drive faults

NOTICE
The monitoring functions F031, F035, F036, and F037 are deactivated in the delivery state.
They can be activated via parameter P820.
F030
Commutation failure or overcurrent has occurred
(active in operating states of – –, I, II)
Possible error causes
♦ Mains voltage dip in regenerative feedback mode
♦ Current control loop not optimized
Fault value:
1
The blocking voltage time area for the commutating
thyristor pair was too small
2
The current crest curve breaks upwards
3
The maximum current value was higher than 250% of
rated device current
4
A paralleled SIMOREG DC Master has detected a
commutation failure or overcurrent
F031
Speed controller monitoring
(active in operating states of – –, I, II)
The monitor responds when the difference between the connectors selected in P590 and P591 (factory setting: Setpoint/actual
value difference of speed controller) exceeds the limit set in parameter P388 for longer than the time set in parameter P390.
Possible fault causes
♦ Open control loop
♦ Controller not optimized
♦ P590 or P591 is not correctly parameterized
9.1.2.6
External faults
F033
Fault message from free function block FB4
(active in all operating states)
Fault value:
1
the binector wired via parameter U102 Index.001 is in the state log."1"
2
the binector wired via parameter U102 Index.002 is in the state log."1"
3
the binector wired via parameter U102 Index.003 is in the state log."1"
4
the binector wired via parameter U102 Index.004 is in the state log."1"
Siemens Energy & Automation
SIMOREG DC Master Base Drive Panel Operating Instructions
Description
Further information (r047.002 to r047.016)
r047 Index 002 to 016:
i002 Delay angle (K0100) in case of error
i003 Actual EMF (K0287) in case of error
i004 Trigger circuitry diagnostics (K0989) in case of error
i005 Actual field current (K0265) in case of error
i006 Number of pulses (K0105) in case of error
9-9