Field Reversal; Input Quantities For Signals; P590 Source For Setpoint Of “Nset = Nact Signal 1”; P591 Source For Actual Value Of "N-Set = N-Act Signal 1" - Siemens 6RA70 Series Instructions Manual

Microprocessor-based converters from 15a to 1680a for variable speed dc drives
Hide thumbs Also See for 6RA70 Series:
  • Faq (4 pages)
Table of Contents

Advertisement

PNU
Description

10.32 Field reversal

(see also Section 9 of Operating Instructions 6RX1700-0AD**)
P580
Source for selection of "Direction of rotation reversal using field
*
reversal"
BDS
Selection of binector to control the "Direction of rotation reversal using field
reversal" function
(G200)
0 = binector B0000
1 = binector B0001
etc.
Signal 0: Positive field direction is selected (B0260 = 1, B0261 = 0),
actual speed value is not inverted
Signal 1: Negative field direction is selected (B0260 = 0, B0261 = 1),
actual speed value is inverted
P581
Source for selection of "Braking with field reversal"
*
Selection of binector to control the "Braking with field reversal" function
BDS
0 = binector B0000
1 = binector B0001
(G200)
etc.
Signal change 0→1: Reversal of field direction (causes braking);
P582
Source for selection of "Field reversal"
*
Selection of binector to control "Field reversal" function
BDS
0 = binector B0000
1 = binector B0001
(G200)
etc.
Signal 0: Positive field direction is selected (B0260 = 1, B0261 = 0)
Signal 1: Negative field direction is selected (B0260 = 0, B0261 = 1)
P583
Source for actual speed signal for field reversal logic
*
Selection of connector to be used as actual speed value for the field
(G200)
reversal logic.
0 = binector B0000
1 = binector B0001
etc.

10.33 Input quantities for signals

(see also Section 8, Sheet G187 and G188 of Operating Instructions 6RX1700-0AD**)
P590
Source for setpoint of "nset = nact signal 1"
*
Setpoint/actual value deviation signal:
Selection of connector to be injected as input quantity "n set " for the
(G187)
setpoint/actual value deviation signal.
0 = connector K0000
1 = connector K0001
etc.
P591
Source for actual value of "n-set = n-act signal 1"
*
Setpoint/actual value deviation signal:
Selection of connector to be injected as input quantity "n act " for the
(G187)
setpoint/actual value deviation signal.
0 = connector K0000
1 = connector K0001
etc.
10-58
When n<n-min is reached, the original field direction is
selected again. The drive switches to state o7.2
Value range
[Unit]
Steps
All binector numbers
1
All binector numbers
1
All binector numbers
[SW 1.9 and later]
1
All connector
[SW 1.9 and later]
numbers
1
All connector
numbers
1
All connector
numbers
1
SIMOREG DC Master Base Drive Panel Operating Instructions
No. indices
See
Factory
Change
setting
(Access /
Type
Status)
Ind: 2
P052 = 3
FS=0
P051 = 40
Type: L2
Offline
Ind: 2
P052 = 3
FS=0
P051 = 40
Type: L2
Offline
Ind: 2
P052 = 3
FS=0
P051 = 40
Type: L2
off-line
Ind: None
P052 = 3
FS=167
P051 = 40
Type: L2
off-line
Ind: None
P052 = 3
FS=174
P051 = 40
Type: L2
Offline
Ind: None
P052 = 3
FS=167
P051 = 40
Type: L2
Offline