PNU
Description
Speed controller
P609
Source for actual speed controller value
*
Selection of connector to be injected as the actual speed controller value
when P083=4
(G151)
0 = connector K0000
1 = connector K0001
etc.

Setting values for configuring of closed-loop field and EMF control

P610
Source for gating unit input (field)
*
Selection of connector to be applied to the gating unit input (field)
(G166)
0 = connector K0000
1 = connector K0001
etc.
P611
Source for field current controller setpoint
*
Limitation at EMF controller output:
(G165)
Selection of connectors to be injected as the field current controller
setpoint. The connectors selected in the four indices are added.
0 = connector K0000
1 = connector K0001
etc.
P612
Source for actual field current controller value
*
Selection of connectors to be injected as the field current controller actual
(G166)
value. The two values are added.
0 = connector K0000
1 = connector K0001
etc.
P613
Source for variable field current setpoint upper limit
*
Limitation at EMF controller output
(G165)
Selection of connector to be injected as the variable field current setpoint
upper limit
i001..i004 Normalization:
100% of the connector value corresponds to the rated
excitation current of the motor (P102)
i005
Normalization:
100% of the connector value corresponds to the actual
converter rated DC current (field) (r073.002)
[can be set in SW 1.9 and later]
0 = connector K0000
1 = connector K0001
etc.
P614
Source for variable field current setpoint lower limit
*
Limitation at EMF controller output
(G165)
Selection of connector to be injected as the variable field current setpoint
lower limit
i001..i004 Normalization:
100% of the connector value corresponds to the minimum
excitation current of the motor (P103)
i005
Normalization:
100% of the connector value corresponds to the actual
converter rated DC current (field) (r073.002)
[can be set in SW 1.9 and later]
0 = connector K0000
1 = connector K0001
etc.
10-62
Value range
[Unit]
Steps
All connector
numbers
1
All connector
numbers
1
All connector
numbers
1
All connector
numbers
1
All connector
numbers
1
All connector
numbers
1
SIEMENS Energy & Automation
SIMOREG DC Master Base Drive Panel Operating Instructions
No. indices
See
Factory
Change
setting
(Access /
Type
Status)
Ind: None
P052 = 3
FS=0
P051 = 40
Type: L2
Offline
Ind: None
P052 = 3
FS=252
P051 = 40
Type: L2
Offline
Ind: 4
P052 = 3
FS=
P051 = 40
i001: 277
Offline
i002: 0
i003: 0
i004: 0
Type: L2
Ind: 2
P052 = 3
FS=
P051 = 40
i001: 266
Offline
i002: 0
Type: L2
Ind: 5
P052 = 3
FS=1
P051 = 40
Type: L2
Offline
Ind: 5
P052 = 3
FS=1
P051 = 40
Type: L2
Offline