P641 Source For Selection Of "Bypass Ramp-Function Generator”; P643 Source For Variable Negative Limitation Of Main Setpoint; P646 Source For Enable Signal For Ramp-Up Integrator Switchover; P647 Source For Enable Signal For Ramp-Function Generator Tracking - Siemens 6RA70 Series Instructions Manual

Microprocessor-based converters from 15a to 1680a for variable speed dc drives
Hide thumbs Also See for 6RA70 Series:
  • Faq (4 pages)
Table of Contents

Advertisement

PNU
Description
P641
Source for selection of "Bypass ramp-function generator"
*
Selection of binector to control the "Bypass ramp-function generator"
BDS
function
(G136)
0 = binector B0000
1 = binector B0001
etc.
P642
Source for variable positive limitation of main setpoint
*
Selection of connectors to be injected at the variable positive limitation of
the main setpoint.
(G135)
The lowest value in each case of the connectors selected via the 4 indices
is applied as the limit.
Note: Negative values at the selected connectors result in a negative
maximum value at the output of the limitation.
0 = connector K0000
1 = connector K0001
etc.
P643
Source for variable negative limitation of main setpoint
*
Selection of connectors to be injected at the variable negative limitation of
the main setpoint.
(G135)
The lowest value in each case of the connectors selected via the 4 indices
is applied as the limit.
Note: Positive values at the selected connectors result in a positive
minimum value at the output of the limitation.
0
= connector K0000
...
8
= connector K0008
= value as set in parameter P642 ∗ ( − 1)
9
10 = connector K0010
etc.
P644
Source for main setpoint
*
Selection of connector to be injected as the main setpoint
FDS
0 = connector K0000
1 = connector K0001
(G135)
etc.
P645
Source for additional setpoint
*
Selection of connector to be injected as an additional setpoint
FDS
0 = connector K0000
1 = connector K0001
(G135)
etc.
P646
Source for enable signal for ramp-up integrator switchover
*
Selection of binector to control enabling of the ramp-function integrator
BDS
switchover function.
(G136)
0 = binector B0000
1 = binector B0001
etc.
P647
Source for enable signal for ramp-function generator tracking
*
BDS
Selection of binector to control enabling of the ramp-function generator
tracking function.
(G136)
0 = binector B0000
1 = binector B0001
etc.
10-66
Value range
[Unit]
Steps
All binector numbers
1
All connector
numbers
1
All connector
numbers
1
All connector
numbers
1
All connector
numbers
1
All binector numbers
1
All binector numbers
1
[SW 2.1 and later]
SIMOREG DC Master Base Drive Panel Operating Instructions
No. indices
See
Factory
Change
setting
(Access /
Type
Status)
Ind: 2
P052 = 3
FS=0
P051 = 40
Type: L2
Offline
Ind: 4
P052 = 3
FS=2
P051 = 40
Type: L2
Offline
Ind: 4
P052 = 3
FS=9
P051 = 40
Type: L2
Offline
Ind: 4
P052 = 3
FS=206
P051 = 40
Type: L2
Offline
Ind: 4
P052 = 3
FS=0
P051 = 40
Type: L2
Offline
Ind: 2
P052 = 3
FS=1
P051 = 40
Type: L2
Offline
Ind: 2
P052 = 3
FS=1
P051 = 40
Type: L2
Offline
SIEMENS Energy & Automation

Advertisement

Table of Contents
loading

Table of Contents