PNU
Description
P053
Control word for the permanent memory
*
Disabling or enabling write accesses to the permanent memory
i001:
Disabling or enabling write accesses to the parameter memory
0
Only save parameter P053 in the permanent memory;
parameter changes are active immediately but the changed
values are only stored temporarily and are lost when the
electronics supply voltage is switched off
1
Save all parameter values in the permanent memory
i002:
Disabling or enabling write accesses to the memory of the
nonvolatile process data
0
Do not save nonvolatile process data in the permanent
memory
1
Save all nonvolatile process data in the permanent memory
If the nonvolatile process data are not stored (P053.002=0),
data are lost when the electronics supply of the SIMOREG DC
Master is switched off, i.e. they have the value 0 after the
electronics supply is switched on again:
K0240: Setpoint of the motor potentiometer
K0309: Motor heating
K0310: Thyristor heating
K9195: Output of the 1st tracking/storage element
K9196: Output of the 2nd tracking/storage element
P054
OP1S – Background lighting
0
ON continuously
1
ON when panel is in use
P055
Copy function data set
*
This parameter allows parameter set 1, 2, 3 or 4 to be copied to parameter
set 1, 2, 3 or 4. This function is applicable only to parameters with 4 indices
(G175)
in the function data set (see also Section 9.1, Data sets and Section 9.11,
and Section 8, Sheet G175).
0xy
Do nothing, automatic resetting value at the end of a copy
operation.
1xy
The contents of parameter set x (source data set, x=1, 2, 3 or 4)
are copied to parameter set y (target data set, y=1, 2, 3 or 4)
(parameter set x remains unchanged, the original contents of
parameter set y are overwritten).
x and y are the respective parameter set numbers (1, 2, 3 or 4)
of the source and target parameter sets.
The copy operation is started by switching P055 over into parameter mode
when P055=1xy.
During the copy operation, the numbers of the parameters being copied are
displayed on the operator panel (PMU).
At the end of the copy operation, P055 is reset to P055=0xy.
r056
Display of active function data set
(G175)
P057
Copy Bico data set
*
This parameter allows parameter set 1 or 2 to be copied to parameter set 1
or 2. This function is applicable only to parameters with 2 indices in the Bico
(G175)
data set (see also Section 9.1, Data sets and Section 9.11, and Section 8,
Sheet G175).
0xy
Do nothing, automatic resetting value at the end of a copy
operation.
1xy
The contents of parameter set x (source data set, x=1 or 2) are
copied to parameter set y (target data set, y=1 or 2) (parameter
set x remains unchanged, the original contents of parameter set
y are overwritten).
x and y are the respective parameter set numbers (1 or 2) of the
source and target parameter sets.
The copy operation is started by switching P057 over into parameter mode
when P057=1xy.
During the copy operation, the numbers of the parameters being copied are
displayed on the operator panel (PMU).
At the end of the copy operation, P057 is reset to P057=0xy.
r058
Display of active Bico data set
(G175)
10-12
Value range
[Unit]
Steps
[SW 1.7 and later]
0 to 1
1
0, 1
011 to 143
1
1 to 4
1
011 to 121
1
1 to 2
1
SIMOREG DC Master Base Drive Panel Operating Instructions
No. indices
See
Factory
Change
setting
(Access /
Type
Status)
Ind: 2
P052 = 3
FS=1
P051 = 0
Type: O2
on-line
Ind: None
P052 = 3
FS=0
P051 ≥ 0
Type: O2
Online
Ind: None
P052 = 3
FS=012
P051 = 40
Type: L2
Offline
Ind: None
P052 = 3
Type: O2
Ind: None
P052 = 3
FS=012
P051 = 40
Type: L2
Offline
Ind: None
P052 = 3
Type: O2
SIEMENS Energy & Automation