Base Drive Panel, 1660 Amps, 1 & 4 Quad Schematics - Siemens 6RA70 Series Instructions Manual

Microprocessor-based converters from 15a to 1680a for variable speed dc drives
Hide thumbs Also See for 6RA70 Series:
  • Faq (4 pages)
Table of Contents

Advertisement

BASE DRIVE PANEL, 1660 AMPS, 1 & 4 QUAD
L1
1CFU-2CFU
2.5A,600V
1CTR
A1-FUF-AFA-011
H1 H2 H3 H4
3CFU
1.5A,250V
3CFU
A1-FUF-DKA-GBP
230 V
XF
X2
EN
M1
M2
MSP
ENSP
MREC
M1
M2
XP
XP
XR
XR
5U1 5W1
109
110
5N1
PWR SUPPLY
PWR SUPPLY
POWER MODULE
K1
CATALOG NO. 6RA7095-4GS22-0Z+X01, (1-QUAD)
CATALOG NO. 6RA7095-4GV62-0Z+X01, (4-QUAD)
ENABLE
106
38
X171
XS
EN
94
93
J5
CTB
EN
90
91
#4 AWG, 60 C
TORQUE TO
11 INCH- LBS
Siemens Energy & Automation
SIMOREG DC Master Base Drive Panel Operating Instructions
CUSTOMER SUPPLIED
IF APPLICABLE
L2
CONTROL
TRANSFORMER
250VA
A1-TRC-Q0C-286
85
82
J1
CTB
J2
84
83
ENABLE RELAY
3RH1122-1AP60
SUPPRESSOR
3RT1916-1BD00
RECT.BR
A1-116-002-001
50A,700V
DC CONTACTOR
A1-FUF-END-C50
A1-CRD-CAC-010
XP
XF1-2
XF1-1
3U1
3W1
FIELD SUPPLY
E-STOP
105
3C
3D
XS
XF2-2
XF2-1
F(-)
F(+)
80
81
460 VAC
6 - #500 MCM,75 C
TORQUE TO
375 INCH- LBS
J6
CTB
L1
L2
L3
96
97
H1
H2
460 V
X1
L1
T1
1U1 1V1 1W1
4U1
SEMICONDUCTOR
FUSES ARE INTERNAL
TO POWER MODULE
Note:
ARMATURE
FAN MUST ROTATE COUNTER-CLOCKWISE
SUPPLY
WHEN VIEWED FROM ABOVE
1C1
1D1
M1
M2
A1
A2
6 - #500 MCM, 75 C
TORQUE TO
375 INCH- LBS
MOTOR = 500 VOLTS DC
F.L.A. = 1660 AMPS DC
J7
J8
CTB
98
99
100
101
5A,600V
A1-FUF-AFA-016
H3
H4
H1
H2
H3
H4
TRANSFORMERS
A1-TRC-Q0C-289
460 V
X2
X1
X2
L2
L3
1.1-1.6A
3RV1011-1AA10
SET@1.50A
T2
T3
4V1
4W1
FAN
SUPPLY
CONTROL
750VA
MSP
7-13

Advertisement

Table of Contents
loading