8.6

Start-up procedure

WARNING
The Base Drive Panel is at a hazardous voltage level even when the line contactor is open.
The gating board (board mounted directly to lower part of housing) has many circuits at
hazardous voltage levels.
Non-observance of the safety instructions given in this manual can result in death, severe
personal injury or substantial property damage.
The following steps summarize the start-up procedure.
Always begin by defaulting the parameters back to the factory value as outlined in paragraph 8.5
Step
Procedure
1
Set P051 = 40 to gain access to change parameters
2
Set P067 = 5 for US rating. This parameter setting is mandatory on Base Drive
Panels.
3
Set the actual operating AC supply voltage for the armature and field converters (P078)
4
Input motor data (P100, P101, P102, P114)
5
Select speed feedback method (P083) [analog tach, encoder, EMF voltage, custom]
6
Select field control and weakening (P081, P082)
7
Set current limits and ramp generator time (P171, P172, P303, P304, P305, P306)
8
Perform self tuning (P051 = 25, 26, 27, 28)
9
Set application specific parameters
10
Documentation of final parameter values
The following details explain how to do each of the above steps.
Siemens Energy & Automation
SIMOREG DC Master Base Drive Panel Operating Instructions
8-9