General Technical Specifications
7.3

Mechanical and climatic environmental conditions

Climatic environmental conditions
The following climatic environmental conditions apply:
Environmental conditions Operating ranges
Temperature
Temperature change
Relative humidity
Air pressure
Contaminant concentration
* Restrictions for the operating range of 0 to 55
The operating range of 0 to 55_C in a vertical installation position is only permitted
for the following modules:
• IM151-1 STANDARD: 6ES7 151-1AA02-0AB0
• PM-E 24 VDC: 6ES7 138-4CA00-0AA0
• 2DI 24 VDC Standard: 6ES7 131-4BB00-0AA0
• 2DI 24 VDC High Feature: 6ES7 131-4BB00-0AB0
• 4DI 24 VDC Standard: 6ES7 131-4BD00-0AA0
• 4DI 24 VDC High Feature: 6ES7 131-4BD00-0AB0
• 2DO 24 VDC/0.5 A Standard: 6ES7 132-4BB00-0AA0
• 2DO 24 VDC/0.5 A High Feature: 6ES7 132-4BB00-0AB0
• 4DO 24 VDC/0.5 A High Feature: 6ES7 132-4BD00-0AA0
• 2DO 24 VDC/2 A Standard: 6ES7 132-4BB30-0AA0
• 2DO 24 VDC/2 A High Feature: 6ES7 132-4BB30-0AB0
• 4DO 24 VDC/2 A Standard: 6ES7 132-4BD30-0AA0
• 2RO NO 24-120 VDC/5 A 24-230 VAC/5 A: 6ES7 132-4HB00-0AB0
Note
All of the supply and load voltages of the ET 200S must not exceed 24 VDC. This
voltage limit must be enforced.
7-8
from 0 to 60_C
from 0 to 40_C
From 0 to 55_C
(see restrictions below)*
10 K/h
From 15 % to maximum 95 %
From 1080 hPa to 795 hPa
SO
: < 0.5 ppm;
2
rel. humidity < 60 %, no dewing
H
S: < 0.1 ppm;
2
rel. humidity < 60 %, no dewing
Remarks
For horizontal installation
For all other mounting positions
For vertical installation
Without condensation
Corresponds to an altitude of
--1000 m to 2000 m
Test:
10 ppm; 4 days
1 ppm; 4 days