Brief Instructions on Commissioning ET 200S
Configuration
1. Start SIMATIC Manager, and create a new project with an I/O controller
(CPU 317-2 PN/DP, for example). Create OB 1, OB 82 and OB 83 for the
project.
2. In HW CONFIG open the window Properties - - Ethernet interface and create
a subnet, for example, Ethernet(1).
3. From the hardware catalog add the IM151-3 PN from the ET 200S catalog on
Ethernet(1):PROFINET IO system (100).
4. Drag the various ET 200S modules from the hardware catalog to the
configuration table.
Table 2-2
Configuration table in HW CONFIG for PROFINET IO
Module
0
6ES7 151-3AA00-0AB0 IM151-3 PN
1
6ES7 138-4CA00-0AA0 PM-E 24 VDC
2
6ES7 131-4BB00-0AB0 2DI 24 VDC
3
6ES7 131-4BB00-0AB0 2DI 24 VDC
4
6ES7 131-4BB00-0AB0 2DI 24 VDC
5
6ES7 131-4BB00-0AB0 2DI 24 VDC
6
6ES7 138-4CA00-0AA0 PM-E 24 VDC
7
6ES7 132-4BB00-0AB0 2DO 24 VDC
8
6ES7 132-4BB00-0AB0 2DO 24 VDC
9
6ES7 132-4BB00-0AB0 2DO 24 VDC
10
6ES7 132-4BB00-0AB0 2DO 24 VDC
5. Set the following parameters:
-- In the properties IO device dialog box for the PM-E 24 VDC,
module 1 (in the configuration table)
Diagnosis: Load voltage not present
-- In the I/O device properties dialog box for 2 DO 24 VDC,
Module 7 (in the configuration table)
Diagnosis: wire break A0
6. Compile and save the configuration.
2-14
Order number
I
O
address
address
0
1
2
3
0
1
2
3
ET 200S Distributed I/O System
Comment
Power module
Bits 0.0 and 0.1
Bits 1.0 and 1.1
Bits 2.0 and 2.1
Bits 3.0 and 3.1
Power module
Bits 0.0 and 0.1
Bits 1.0 and 1.1
Bits 2.0 and 2.1
Bits 3.0 and 3.1
EWA-4NEB 780602402-12