Rated voltage for operation
The ET 200S distributed I/O system works with the rated voltage and
corresponding tolerances specified in the following table.
ET 200S modules
Everything except
motor starters
t
t t
1)
static value: generation as functional extra-low voltage with safe electrical
isolation as per IEC 60364-4-41
2)
dynamic value: including ripple e. g. with three-phase bridge rectification
7.5
Variations in technical data for the

ET 200S FC frequency converter

The following table shows variations in the general technical data for the
ET 200S FC frequency converter compared to the ET 200S.
Table 7-2
Standards, certificates and approvals
Shipping and storage conditions
Climatic ambient conditions
Mechanical ambient conditions
Rated operational voltage
Use in Zone 2
ET 200S Distributed I/O System
EWA-4NEB 780602402-12
Rated voltage
24 VDC
120 VAC
230 VAC
Variations in technical data for the ET 200S FC frequency
converter
Chapter
General Technical Specifications
Tolerance range
20.4 to 28.8 VDC
18.5 to 30.2 VDC
VAC to 132 VAC (47 Hz to 63 Hz)
VAC to 264 VAC (47 Hz to 63 Hz)
different values
The frequency converter is not approved
under
cULus for HAZ.LOC.
FM (Factory Mutual Research)
shipbuilding
Free fall: ≤ 0.35 m
Temperature for horizontal installation:
from 0 to 60 °C
Temperature for vertical installation:
from 0 to 40 °C
See operating manual for ET 200S FC
frequency converter
frequency converter
(6SL3 298-0CA12-0xP0)
The ET 200S FC frequency converter is not
approved for operation in Zone 2 hazardous
atmosphere.
1)
2)
7-11