Analog Electronic Modules
Measuring range - - temperature coefficient - - measuring range
The following table shows which temperature coefficients and which measuring
ranges can be configured for the specific measuring type:
Measurement type
disabled
4-wire resistor
3-wire resistor
2-wire resistor
3-wire thermal resistor
1)
The preceding temperature coefficient are applicable for Europe.
12-36
Temperature coefficient
--
--
--
Pt 0.003850/ Pt 0.003916 /
Pt 0.003902 / Pt 0.003920 /
1)
Pt 0.003851
1)
Ni 0.006180
/ Ni 0.006720
Ni 0.005000
1)
Cu 0.00427
Measuring range
--
150 Ω / 300 Ω / 600 Ω / 3000 Ω
150 Ω / 300 Ω / 600 Ω / 3000 Ω /
PTC
Pt100 climate range /
Pt100 standard range /
Pt200 climate range /
Pt200 standard range /
Pt200 standard range /
Pt500 climate range /
Pt500 standard range /
Pt1000 climate range /
Pt1000 standard range
Ni100 climate range /
NI100 standard range /
Ni120 climate range /
Ni120 standard range /
Ni200 climate range /
Ni200 standard range /
Ni500 climate range /
Ni500 standard range /
Ni1000 climate range /
Ni1000 standard range
2)
Ni 1000 climate range
2)
Ni 1000 standard range
Cu10 climate range /
Cu10 standard range