Measuring range for thermocouple type K
Table 12-18 SIMATIC S7 Format: Measuring range type K in °C and °F
Units
T pe K
Type K
decimal
in °C
> 1622,0
32767
1622,0
16220
:
:
1372,1
13721
1372,0
13720
:
:
- -270,0
- -2700
< - -270,0
- - 32768
Measuring range for thermocouple type L
Table 12-19 SIMATIC S7 Format: Measuring Range Type L in °C and °F
Units
T pe L
Type L
decimal
in °C
> 1150,0
32767
1150,0
11500
:
:
900,1
9001
900,0
9000
:
:
- -200,0
- -2000
< - -200,0
- -32768
ET 200S Distributed I/O System
EWA-4NEB 780602402-12
T pe K
Type K
hexa
in °F
decimal
7FFF
> 2951,6
H
3F5C
2951,6
H
:
:
3599
2501,7
H
3598
2501,6
H
:
:
F574
- -454,0
H
8000
< - -454,0
H
T pe L
Type L
hexa
in °F
decimal
7FFF
> 2102,0
H
2CEC
2102,0
H
:
:
2329
1652,1
H
2328
1652,0
H
:
:
F830
- -328,0
H
8000
< - -328,0
H
Units
decimal
hexa
decimal
32767
7FFF
Overflow
H
29516
734C
H
:
:
Overshoot range
25062
61B9
H
25061
61B8
H
:
:
Nominal range
- -4540
EE44
H
- - 32768
8000
Underflow
H
Units
decimal
hexa
decimal
32767
7FFF
Overflow
H
21020
521C
H
:
:
Overshoot range
16521
4089
H
16520
4088
H
:
:
Nominal range
- -3280
F330
H
- -32768
8000
Underflow
H
Analog Electronic Modules