Parameters For Analog Output Modules U, I - Siemens SIMATIC ET 200S Manual

Distributed i/o system
Hide thumbs Also See for SIMATIC ET 200S:
Table of Contents

Advertisement

Analog Electronic Modules
Temperature coefficient
The correction factor for the temperature coefficients (α value) indicates the
relative change of the resistance of a specified material if the temperature
increases by 1_C.
The temperature coefficient depends on the chemical composition of the material.
In Europe only one value is used per sensor type (default value).
The additional values enabled sensor-specific adjustment of the temperature
coefficients and therefore even greater precision.
Parameters for
• 2AO U Standard, 2AO U High Feature analog electronic module
• 2AO I Standard, 2AO I High Feature analog electronic module
Table 12-35 Parameters for analog output modules U, I
2AO U
2AO I
Standard
Standard
2AO U High
2AO I High
Feature
Feature
Group diagnostics
(configuration error, internal
error)
Diagnosis:
------
Short circuit
as per M
------
Diagnosis:
Wire break
Response at CPU/master
STOP
Output type /
------
range
------
Output type /
range
1)
Substitute value
1)
If the power to the IM is disconnected and the analog output modules are still powered, the configured
substitute values are output. Substitute values must be within the nominal range. Values from --27648 to
+27648 are configured (when configured with the GSD file).
12-38
Value range
disable
enabled
disable
enabled
disable
enabled
Output without current and
voltage
apply substitute value
hold last value
disabled
1 to 5 V
 10 V
disabled
4 to 20 mA
 20 mA
0 to 65535 (value range must
be within the nominal range)
Default setting
Effective range
disable
Module
disable
Channel
disable
Channel
Output without
Module
current and
voltage
 10 V
Channel
4 to 20 mA
Channel
10 V/ 20 V:
Channel
0 V
4 to 20 mA: 4 mA
1 to 5 V: 1 V
ET 200S Distributed I/O System
EWA-4NEB 780602402-12