Switching Capacity And Service Life Of Relay Contacts - Siemens SIMATIC ET 200S Manual

Distributed i/o system
Hide thumbs Also See for SIMATIC ET 200S:
Table of Contents

Advertisement

Digital Electronic Modules
Switching capacity and service life of contacts
An external protective circuit offers a higher service life that that given in the table:
Table 11-27 Switching capacity and service life of relay contacts
Resistive load
For resistive load
For inductuve load
as per IEC 947-5-1
IEC 947 5 1
DC 13/ AC 15
DC 13/ AC 15
For inductuve load
as per IEC 947-5-1
IEC 947 5 1
DC 13/ AC 15
DC 13/ AC 15
11-80
Voltage
24 VDC
5.0 A
4.0 A
2.0 A
1.0 A
0.5 A
0.1 A
60 VDC
0.5 A
120 VDC
0.2 A
48 VAC
2.0 A
60 VAC
2.0 A
120 VAC
5.0 A
3.0 A
2.0 A
1.0 A
0.5 A
230 VAC
5.0 A
3.0 A
2.0 A
1.0 A
0.5 A
24 VDC
2.0 A
1.0 A
0.5 A
60 VDC
0.5 A
120 VDC
0.2 A
48 VAC
1.0 A
60 VAC
1.0 A
120 VAC
2.0 A
1.0 A
0.5 A
0.1 A
230 VAC
2.0 A
1.0 A
0.5 A
Current
Switching cycles
(typical)
0.1 million
0.2 million
0.5 million
1.6 million
4 million
7 million
1.6 million
1.6 million
1.6 million
1.2 million
0.1 million
0.2 million
0.4 million
0.8 million
1.5 million
0.1 million
0.2 million
0.4 million
0.8 million
1.5 million
0.1 million
0.2 million
0.5 million
0.2 million
0.5 million
0.7 million
0.5 million
0.1 million
0.3 million
1 million
2 million
0.1 million
0.3 million
1 million
ET 200S Distributed I/O System
EWA-4NEB 780602402-12

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents