Siemens SIMATIC ET 200S Manual page 503

Distributed i/o system
Hide thumbs Also See for SIMATIC ET 200S:
Table of Contents

Advertisement

Analog Value Formation
Measurement principle
Integration / conversion
time / resolution per chan-
nel:
Integration time
selectable
Interference frequency
suppression in Hz
Integration time in ms
Basic conversion time
incl. integration time in
ms
Additional conversion
time for wire break
diagnostics in ms
Cycle time in ms
Resolution (incl.
overshoot range)
Interference Suppression, Error Limits
Interference voltage sup-
pression for f= n x
(f11 %), (f1 = interference
frequency)
Common mode
interference (U
)
SS
Common mode
interference
(peak value of
interference < rated
value of the input range)
Crosstalk between inputs
Operational error limit for
80 mV (across complete
temperature range, in rela-
tion to input range)
ET 200S Distributed I/O System
EWA-4NEB 780602402-12
integrating
Yes
60
50
16.7
20
66
80
5
5
Number of active
channels per
module x conversion
time
15 bits + sign
min. 90 dB
min. 70 dB
min. --50 dB
0.1 %
Analog Electronic Modules
Operational error limit for
thermocouple (across com-
plete temperature range, in
1)
relation to input range)
Operational error limit for
thermocouple Type C
(across complete tempera-
ture range, in relation to in-
1)
put range)
Basic error limit for 80 mV
(operational error limit at
25_C, related to the input
range)
Basic error limit for thermo-
couples (operational error
limit at 25_C, related to the
1)
input range)
Basic error limit for thermo-
couple Type C (operational
error limit at 25_C, related
1)
to the input range)
Temperature error (in rela-
tion to input range)
Linearity error (relative to
the input range)
Repetition accuracy
(in transient state at 25_C,
relative to input range)
Total errors limits when us-
ing internal compensation
Operational error limit
(over complete
temperature range in
static thermal state,
ambient temperature
fluctuation
2)
< 0.3 K/min)
Basic error limit
(operational error limit at
25 _C in static thermal
state, ambient
temperature fluctuation
3)
< 0.3 K/min)
1.5 K
7 K
0.05 %
1 K
5 K
0.005 %/K
0.01 %
0.05 %
2.5 K
1.5 K
12-97

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents