Display
Description
Alarm
4
Overload protection active.
1)
The motor or controller temperature is too
high.
P
Error in the learn run
1)
_
Controller waiting for learn run
1)
See Section Drive functions (Page 23).
1)
See Section Operation and parameter assignment (Page 42).
2)
ATE500E
System Manual, 09/2017, A5E33917696-AD
Fault resolution
Allow the motor and controller to cool.
Follow the installation instructions, see Section Installation
(Page 91).
The distance between the door and the CLOSED position
must be less than 10 cm at the start of the learn run.
The door width must be between 30 cm and 5 m.
There must not be any obstructions during the learn run.
Increasing the closing force by reducing the counterweight
by means of the minimal editor.
If there is no valid parameter set (for example at the time of
initial commissioning):
Perform learn run with standard parameters loaded (see Ta-
ble 6-3 Starting a learn run when the supply voltage is ap-
plied (Page 44)).
If a learn run has been canceled:
Repeat the learn run or restart the controller.
Controller
6.9 Diagnostics