Final checks
Final check of the permissible energies and forces.
Risk of injury due to moving mechanical parts
Check permissible forces and energies after the door drive has been commissioned in the
complete system and adjust them if they exceed their limit values.
Please observe the valid applicable standards and directives for the respective application,
as well as the following guidelines:
• The speed limit curve is the characteristic curve which defines the maximum permissible
• Gearing up or down is not allowed on the toothed belt because this would change the
Risk of injury and material damage due to excessive closing or opening force of the door
Exceeding the maximum static closing and opening forces may lead to injuries to persons
or damage to the door drive and to mechanical components of the door.
Taking the counterweights into account, the maximum static closing and opening forces
must not exceed 150 N!
ATE500E
System Manual, 09/2017, A5E33917696-AD
WARNING
door speed, v
, as a function of the total door panel weight.
max
– According to EN 81, the maximum kinetic energy of the door in the closing direction
must not exceed 10 joules.
– According to EN 81, the maximum kinetic energy of the door must not exceed
4 joules in the closing direction if the reversing device is disabled and every closing
operation must be signaled acoustically. An acoustic signal is not part of the
SIDOOR system and must be provided and ensured by the operator.
kinetic energies or static forces on the door. The door width would then no longer be
valid.
WARNING
Connection and commissioning
141