Precautions With Connecting Two-Wire Dc Sensors; A-3-1 Relation Between On Voltage Of A Unit With Dc Inputs And Sensor Residual Voltage; A-3-2 Relation Between On Current Of A Unit With Dc Inputs And Sensor Control Output; Current - Omron GX-ID1611 User Manual

Gx-series, ethercat remote i/o terminal ethercat slave units
Table of Contents

Advertisement

A Appendix
A-3 Precautions with Connecting
Two-wire DC Sensors
When using a two-wire DC sensor with a DC input type Slave Unit, check that the following conditions
have been met. Failure to meet these conditions may result in operating errors.
A-3-1
Relation between ON Voltage of a Unit with DC Inputs and Sensor
Residual Voltage
≤ V
V
- V
ON
CC
R
V
: I/O power supply voltage (The allowable power supply voltage range is 20.4 to 26.4 V, so 20.4 V will be
CC
used here to allow for the worst possible conditions.)
V
: ON voltage for a Unit with DC inputs
ON
V
: Sensor's output residual voltage
R
It is sometimes possible to satisfy the above equation by adjusting the I/O power supply voltage (V
to 26.4 V.
A-3-2
Relation between ON Current of a Unit with DC Inputs and Sensor
Control Output
(min) ≤ I
I
OUT
ON
I
: Sensor control output (load current)
OUT
I
: ON current of a Unit with DC inputs
ON
I
is calculated as follows:
ON
I
= (V
ON
CC
V
: Internal residual voltage of a Unit with DC inputs
F
R
: Input impedance of a Unit with DC inputs
IN
When I
is smaller than I
ON
The bleeder resistor constant can be calculated using the following equation.
R ≤ (V
- V
) / (I
CC
R
Power W ≥ (V
CC
2-wire
V
sensor
A - 76
≤ I
(max)
OUT
- V
- V
) / R
R
F
IN
(min), connect a bleeder resistor R.
OUT
(min) - I
)
OUT
ON
2
− V
/ R × 4 [allowable margin]
)
R
DC input
R
R
R
IN
type slave
V
CC
GX-series EtherCAT Slave Unit User's Manual
)
CC